Daikin FXM125LVE [192/254] Troubleshooting op central remote controller

Daikin FXYB20KV1 [192/254] Troubleshooting op central remote controller
Si38-606 Troubleshooting (OP: Central Remote Controller)
Troubleshooting 181
3. Troubleshooting (OP: Central Remote Controller)
3.1
M1
PC Board Defect
Remote
Controller
Display
M1
Applicable
Models
Centralized remote controller
Method of
Malfunction
Detection
Detect an abnormality in the DIII-NET polarity circuit.
Malfunction
Decision
Conditions
When + polarity and - polarity are detected at the same time.
Supposed
Causes
Defect of central remote controller PC board
Troubleshooting Replace the central remote controller PC board.