Daikin FXF125LVE [67/254] Low pressure protection control

Daikin FXS50LVE [67/254] Low pressure protection control
Protection Control Si38-606
56 Function
4.2 Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
[In cooling operation].
Low pressure not limited
Pe<0.16MPa
Low pressure standby
Low pressure limited
52 Hz + OFF
Pe<0.12MPa
Pe>0.20MPa
Pe<0.01MPa
Pe: LP pressure sensor detection
value
When occurring 3 times within 30 min.,
the malfunction code E4 is output.