Daikin FXF125LVE [126/254] The system operates for malfunction codes indicated in black squares however be sure to check and repair

Daikin FXMQ250MAVE [126/254] The system operates for malfunction codes indicated in black squares however be sure to check and repair
Si38-606 Troubleshooting by Remote Controller
Troubleshooting 115
Outdoor
Unit
LA 999Malfunction of power unit
LC 999Malfunction of transmission between inverter and
control PC board
157
P1 999Inverter over-ripple protection 159
P4 999Malfunction of inverter radiating fin temperature rise
sensor
160
PJ 999Faulty field setting after replacing main PC board or
faulty combination of PC board
161
System U0 879Low pressure drop due to refrigerant shortage or
electronic expansion valve failure
162
U1 999Reverse phase / open phase 163
U2 999Power supply insufficient or instantaneous failure 164
U3 999Check operation is not conducted. 166
U4 999Malfunction of transmission between indoor and
outdoor units
167
U5 999Malfunction of transmission between remote
controller and indoor unit
169
U5 787Failure of remote controller PC board or setting
during control by remote controller
169
U7 999Malfunction of transmission between outdoor units 170
U8 997Malfunction of transmission between master and
slave remote controllers (malfunction of slave remote
controller)
172
U9 999Malfunction of transmission between indoor unit and
outdoor unit in the same system
173
UA 999Excessive number of indoor units etc. 175
UC 888Address duplication of central remote controller 176
UE 999Malfunction of transmission between central remote
controller and indoor unit
177
186
UF 999Refrigerant system not set, incompatible wiring /
piping
179
UH 999Malfunction of system, refrigerant system address
undefined
180
Centralized
Control and
Schedule
Timer
M1 8 or 79 9PC board defect 181
188
M8 8 or 79 9Malfunction of transmission between optional
controllers for centralized control
182
189
MA 8 or 79 9Improper combination of optional controllers for
centralized control
183
190
MC 8 or 79 9Address duplication, improper setting 185
192
Heat
Reclaim
Ventilation
64 879Indoor unit’s air thermistor error
65 879Outside air thermistor error
68 879
6A 879Damper system alarm
6A 999Damper system + thermistor error
6F 879Malfunction of simple remote controller
6H 879Malfunction of door switch or connector
94 999Internal transmission error
Malfunction
code
Operation
lamp
Inspection
display
Unit No. Malfunction contents Page