ED39-865 Fan Performances
FXMQ-P (R-410A) 67
2
FXMQ100PVE
FXMQ125PVE
Notes :
1. As for this machine, less than 10% of the volume of blow-off air is
automatically adjusted to the rated quantity by airflow auto adjustment at the
time of installation.
2. After duct construction completion, please perform local setting "airflow auto
adjustment" by remote controller.
3. About the local setting method of the "airflow auto adjustment", look at the
installation manual which is attached to an indoor unit.
4. External static pressure that can adjust by "airflow auto adjustment" function
is 50Pa - 200Pa (When air flow is HH).
5. It is not operated auto adjustment, operated in air flow that is different from
rated quantity in the case of use out of external static pressure range
mentioned above.
6. This figure shows a fan characteristics at the time of "HH" "H" and "L".
7. The remote controller can be used to change "HH" "H" and "L".
8. ESP : external static pressure.
2420 373422
(Pa)
2826 363230
Upper limit of ESP
(NOTE 8)
5
20
(mmH2O)
15
20
(mmH2O)
(mmH
2O)
0
5
10
0
200
(mmH2O)
25
100
25
External static pressure
(Pa)
0
10
15
50
150
250
Air flow (m
3
/min)
Lower limit of ESP
[ L ]
[ H ]
[ HH ]
Upper limit
of ESP by
airflow auto
adjustment
Lower limit
of ESP by
airflow auto
adjustment
3D060581
Notes :
1. As for this machine, less than 10% of the volume of blow-off air is
automatically adjusted to the rated quantity by airflow auto adjustment at the
time of installation.
2. After duct construction completion, please perform local setting "airflow auto
adjustment" by remote controller.
3. About the local setting method of the "airflow auto adjustment", look at the
installation manual which is attached to an indoor unit.
4. External static pressure that can adjust by "airflow auto adjustment" function
is 50Pa - 200Pa (When air flow is HH).
5. It is not operated auto adjustment, operated in air flow that is different from
rated quantity in the case of use out of external static pressure range
mentioned above.
6. This figure shows a fan characteristics at the time of "HH" "H" and "L".
7. The remote controller can be used to change "HH" "H" and "L".
8. ESP : external static pressure.
25
5
20
Air flow (m
3
/min)
23 39
(mmH2O)
15
31
20
(mmH2O)
(mmH
2O)
0
5
10
0
41
200
Lower limit of ESP
(mmH2O)
25
100
25
35
External static pressure
(Pa)
0
33
10
27 29
15
43
50
37
150
250
[ L ]
[ H ]
[ HH ]
Upper limit of ESP
(NOTE 8)
Upper limit
of ESP by
airflow auto
adjustment
Lower limit
of ESP by
airflow auto
adjustment
3D060582