Daikin FXAQ20MAVET [152/264] E4 outdoor unit actuation of low pressure sensor

Daikin FXCQ125M8V3B [152/264] E4 outdoor unit actuation of low pressure sensor
SiBE34-703 Troubleshooting by Indication on the Remote Controller
Troubleshooting 141
3.16 E4 Outdoor Unit: Actuation of Low Pressure Sensor
Remote
Controller
Display
E4
Applicable
Models
RXYSQ4~6P
Method of
Malfunction
Detection
Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Decision
Conditions
Error is generated when the low pressure is dropped under specific pressure.
Operating pressure:0.07MPa
Supposed
Causes
Abnormal drop of low pressure (Lower than 0.07MPa)
Defect of low pressure sensor
Defect of outdoor unit PC board (A1P)
Stop valve is not opened.