SiBE34-703 Troubleshooting by Indication on the Remote Controller
Troubleshooting 153
3.26 J7 Outdoor Unit: Malfunction of Thermistor (R7T) for
Outdoor Unit Liquid Pipe
Remote
Controller
Display
J7
Applicable
Models
RXYSQ4~6P
Method of
Malfunction
Detection
Malfunction is detected from the temperature detected by the liquid pipe thermistor.
Malfunction
Decision
Conditions
When a short circuit or an open circuit in the heat exchange thermistor is detected.
Supposed
Causes
Defect of thermistor (R7T) for outdoor unit liquid pipe
Defect of outdoor unit PC board (A1P)
Troubleshooting
Refer to thermistor resistance / temperature characteristics table on P223.
(V3074)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Resistance
is normal when
measured after
disconnecting the thermistor
(R4T) from the outdoor
unit PC board.
(3.5k~
360k)
Replace outdoor unit PC board
(A1P).
Connect the thermistor and turn
on again.
NO
NO
Replace the thermistor (R6T).
YES
YES
Connector
is connected to X13A of
outdoor unit PC board
(A1P).