Daikin FXAQ20MAVET [165/264] J9 outdoor unit malfunction of subcooling heat exchanger gas pipe thermistor r4t

Daikin FXAQ50MAVET [165/264] J9 outdoor unit malfunction of subcooling heat exchanger gas pipe thermistor r4t
Troubleshooting by Indication on the Remote Controller SiBE34-703
154 Troubleshooting
3.27 J9 Outdoor Unit: Malfunction of Subcooling Heat
Exchanger Gas Pipe Thermistor (R4T)
Remote
Controller
Display
J9
Applicable
Models
RXYSQ4~6P
Method of
Malfunction
Detection
Malfunction is detected according to the temperature detected by subcooling heat exchanger
gas pipe thermistor.
Malfunction
Decision
Conditions
When the subcooling heat exchanger gas pipe thermistor is short circuited or open.
Supposed
Causes
Faulty subcooling heat exchanger gas pipe thermistor (R4T)
Faulty outdoor unit PC board
Troubleshooting
Refer to “Thermistor Resistance / Temperature Characteristics” table on P223.
(V3075)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the
resistance
measured after
removing the thermistor
(R4T) from outdoor unit PC
board normal?
(3.5 k to
360 k)
Replace outdoor unit PC board
(A1P).
Connect connector and operate
unit again.
NO
NO
Replace thermistor (R4T).
YES
YES
Is
the connector
for subcooling heat
exchanger gas pipe
thermistor connected to
X12A of outdoor unit
PC board
(A1P)?