Daikin FXSQ63P7VEB [117/370] State of function units is same as cooling operation of 6 function unit p 0

Daikin FXSQ32PVE [117/370] State of function units is same as cooling operation of 6 function unit p 0
SiBE311209 Special Control
Function 108
<Function Unit>
State of function units is same as “Cooling operation” of 6.1.2 “Function Unit” (P.90)
<Indoor Units>
Part Name Electric symbol Indoor unit actuator operation during cooling oil return operation
Fan M1F
Thermo. ON unit Remote controller setting
Unit not in operation OFF
Thermo. OFF unit Remote controller setting
Electronic
expansion valve
Y1E
Thermo. ON unit Normal opening degree
Unit not in operation Normal opening degree for forced thermostat ON
Thermo. OFF unit 224 pls