Daikin FXSQ63P7VEB [350/370] Fxdq20pb 25pb 32pb 40nb 50nb 63nbve

Daikin FXSQ25P7VEB [350/370] Fxdq20pb 25pb 32pb 40nb 50nb 63nbve
Wiring Diagrams for Reference SiBE311209
341 Appendix
FXDQ20PB / 25PB / 32PB / 40NB / 50NB / 63NBVE
,
POWER SUPPLY
~220-240V
50Hz
X2M
L
N
L
N
RED
BLU
GRN
/YLW
X13A X12A X11A
R1T R2T R3T
X16A
A1P
X30A
X18A
X27A
X1A T1R
X3A
X31A
X7A
X8A
S1L
M
X16AX18A
A1P
C1X1M
Z1C
Z2C
T1R
X2M
Control box
M
HAP
X4A
V1TR
Z1C
N=3
Z2C
N=3
PNK
WHT
YLW
ORG
BLU
BLK
X1M
T2
T1
F2
F1
P2
P1
Note: 3
Input from outside
Note: 1
Transmission wiring
central remote control
Wired remote
control
GRY
PRP
BLU
C1
YLW
WHT
M
RED
BLK
M1F
Q1M
: Terminal
: Connector
NOTES
1 In case of using central remote control, connect it to the unit in accordance with the attached installation manual.
2 Remote control model varies according to the combination system, confirm engineering materials and catalogs, etc. before connecting.
3 When connecting the input wires from outside, forced off or on/off control operation can be selected by remote control.
In details, refer to the installation manual attached to the unit.
BLK: Black
BUL: Blue
GRY: Gray
GRN: Green
Colors: ORG: Orange
PNK: Pink
PRP: Purple
RED: Red
WHT: White
YLW: Yellow
3D060547B
: Field wiring
A1P Printed circuit board R1T Thermistor (air) Z1C•Z2C Noise filter (ferrite core)
C1 Capacitor (M1F) R2T Thermistor (coil - 1) Wired remote control
F1U Fuse (F5A, 250V) R3T Thermistor (coil - 2) R1T Thermistor (air)
HAP
Light emitting diode
(service monitor-green)
S1L Float switch SS1 Selector switch (main/sub)
T1R Transformer (220V/22V) Connector for optional parts
KPR Magnetic relay (M1P) V1TR Phase control circuit X16A Connector (adaptor for wiring)
M1F Motor (indoor fan) X1M Terminal block
X18A
Connector (wiring adaptor for electrical
appendices)
M1P Motor (drain pump) X2M Terminal block
Q1M Thermal protector (M1F embedded) Y1E Electronic expansion valve
F1U
Y1E
M1P
P2
P1
R1T
SS1

Содержание

Скачать