Daikin FXSQ63P7VEB [133/370] Freeze up prevention

Daikin FXSQ50P7VEB [133/370] Freeze up prevention
SiBE311209 Outline of Control (Indoor Unit)
Function 124
9.4 Freeze-up Prevention
Freeze-up
Prevention by Off
Cycle (Indoor
Unit)
When the temperature detected by liquid pipe temperature thermistor (R2T) of the indoor unit
heat exchanger drops too low, the unit enters freeze-up prevention operation in accordance with
the following conditions, and is also set in accordance with the conditions given below.
When freeze-up prevention is activated, the electronic expansion valve is closed, the drain
pump turns ON and the fan tap is fixed to L airflow. When the following conditions for stopping
are satisfied, it returns.
Conditions for starting freeze-up prevention: Temperature is -1°C or less for total of 40 min., or
temperature is -5°C or less for total of 10 min.
Conditions for stopping freeze-up prevention: Temperature is +7°C or more for 10 min.
continuously
[Conditions for starting when airflow direction is two-way or three-way]
Conditions for starting: Temperature is 1ºC or less for a total of 15 minutes or 0ºC or less for 1
minute continuously.
+7ºC
0ºC
–5ºC
OR
+7ºC
–1ºC
t1 t2 t3
t > 40min.
0ºC
Freeze-up prevention operation
Forced OFF by thermostat
10 min.
Freeze-up prevention operation
Forced OFF by thermostat
10 min.
10 min.
t4
+7ºC
0ºC
OR
+7ºC
+1ºC
t1 t2 t3 t >15min.
Freeze-up prevention operation
Forced OFF by thermostat
10 min.
Freeze-up prevention operation
Forced OFF by thermostat
1 min.
10 min.
t4