Daikin FXSQ63P7VEB [261/370] Suction pipe thermistor r8t abnormality

Daikin FXSQ140PVE [261/370] Suction pipe thermistor r8t abnormality
SiBE311209 Troubleshooting by Indication on the Remote Controller
Service Diagnosis 252
4.28 Suction Pipe Thermistor (R8T) Abnormality
Remote
Controller
Display
J5
Applicable
Models
Outdoor Unit: RTSQ8~16PAY1
Function Unit: BTSQ20PY1
Method of Error
Detection
Error is detected from the temperature detected by the suction pipe thermistor.
Error Decision
Conditions
When a short circuit or an open circuit in the suction pipe thermistor is detected
Supposed
Causes
Defective connection of thermistor
Defective outdoor unit suction pipe thermistor (R8T)
Defective outdoor unit PCB (A2P)
Troubleshooting
Refer to P.314.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Connector is
connected to X11A,
of outdoor unit PCB.
(A2P)
NO
YES
Resistance is normal
when measured after
disconnecting the
thermistor (R8T) from
the outdoor unit PCB.
CHECK 11
NO
YES
Connect the connector and turn ON
again.
Replace the thermistor (R8T).
Replace the outdoor unit PCB
(A1P).
CHECK 11