Daikin FXSQ63P7VEB [124/370] Function

Daikin FXSQ50PVE4 [124/370] Function
Outline of Control (Indoor Unit) SiBE311209
115 Function
Micro-computer dry operation
Micro-computer
dry display
7
8
Thermostat
status
OFF
ON
Fan MF :
Operating in L mode
Fan MF :
Operating in L
mode after it stops for 6 min.
Electronic
expansion valve
20E :
Superheated degree control
Electronic
expansion valve
20E :
Closed
(Option)
MP
Drain pump kit
: OFF after 5-min.
residual operation
A
7. Micro-computer dry display
No set temperature and airflow rate of the remote controller are displayed.
8. Thermostat status
Set temperature when operating the micro-computer dry mechanism.
Suction air temperature
ab
9
Fan Operation
(Option)
Drain
pump kit
MP : OFF
Aux. electric
heater
52H : OFF
Mu : OFF
Humidifier
Swing flap
No
10
Yes
Set wind direction
Swing flap
11
Fan MF: Operating
with set airflow rate
Electronic
expansion valve
20E :
Closed
A
9. Fan operation
By setting the remote controller to Fan, the
fan will operate with thermostat OFF in set
temperature control operation mode.
10. Set airflow direction
According to airflow direction instruction from
the remote controller, the airflow direction is set
to 100% horizontal while in heating operation.
11.Fan
According to fan speed instruction from the
remote controller, the fan is put into operation
in LL mode while in heating operation.
Heating Operation
(option)
Drain
pump
kit
MP : OFF
Swing flap?
No
12 Yes
12
Swing flap
Set airflow direction
Is defrost operation in
progress?
Yes
No
13
Yes
Is hot starting in
progress?
No
DEFROST/HOT START
indicating lamp: ON
DEFROST/HOT START
indicating lamp: OFF
Yes
Restart prevention
operating in progress?
(4 min.)
No
Is test run in
progress?
14
(1) (3)
Thermostat
status
(2)
(Option)
Aux. electric
heater
52H : OFF
Mu : OFF
Humidifier
(Option)
Aux. electric
heater
52H : OFF
Mu : ON
Humidifier
(Option)
Aux. electric
heater
52H : ON
Mu : ON
Humidifier
(Option)
Aux. electric
heater
52H : OFF
Mu : OFF
Humidifier
Fan MF :
LL operation
15
Is outdoor air
temperature drop
protection in progress?
Yes
No
Fan MF :
Operating
with set airflow rate
Fan MF :
Operating in L mode
Fan MF :
Stop
Electronic
expansion valve
20E :
Closed
Electronic
expansion valve
20E :
Capacity control
Electronic
expansion valve
20E :
Open
A
12. Airflow direction
When the heating thermostat turns OFF, the airflow direction will be set to 100% horizontal.
13. Hot start
If the condenser inlet temperature exceeds 34°C at the time of starting operation or after the
completion of defrost operation, or until 3 minutes pass or Tc is 52°C or more, hot starting will be
conducted.
14. Thermostat status
(3)
a
(2)
b
-4 -2
(1)
Set temp.
Suction air temp.
15. Outdoor air temperature drop protection
When the set temperature is below 24°C or the electronic expansion valve opening is small, the
protection will be activated.