Daikin FXDQ25NVE [20/218] Slim ceiling mounted built in type

Daikin FXKQ32MVE [20/218] Slim ceiling mounted built in type
SiBE39-402 Specifications
Specifications 11
Slim Ceiling Mounted Built-in Type
Notes: H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp; 35°CDB / Equivalent piping length: 7.5m,
level difference: 0m.
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length; 7.5m,
level difference; 0m. (Heat pump only)
H4 External static pressure is changeable to set by the remote controller this pressure means “High static
pressure - Standard static pressure”.
H5 The operation sound levels are the conversion values in anechoic chamber. In practice, the sound tend to
be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx.
5dBA.
Model FXDQ20NVE FXDQ25NVE FXDQ32NVE
H1 Cooling Capacity (19.5°CWB)
kcal/h 2,000 2,500 3,150
Btu/h 7,900 9,900 12,500
kW 2.3 2.9 3.7
H2 Cooling Capacity (19.0°CWB) kW 2.2 2.8 3.6
H3 Heating Capacity
kcal/h 2,200 2,800 3,400
Btu/h 8,500 10,900 13,600
kW 2.5 3.2 4.0
Casing Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
Dimensions: (H×W×D) mm 200×900×620 200×900×620 200×900×620
Coil (Cross
Fin Coil)
Rows×Stages×Fin Pitch mm 2×12×1.5 2×12×1.5 2×12×1.5
Face Area 0.176 0.176 0.176
Fan
Model
Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output × Number
of Units
W 62×1 62×1 62×1
Air Flow Rate (H/L) m³/min 9.5/7.5 9.5/7.5 10.5/8.5
External Static Pressure Pa 44-15 H4 44-15 H4 44-15 H4
Drive Direct Drive Direct Drive Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Sound Absorbing Thermal Insulation Material Foamed Polyethylene Foamed Polyethylene Foamed Polyethylene
Air Filter Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof Removal / Washable / Mildew Proof
Piping
Connections
Liquid Pipes mm φ6.4 (Flare Connection) φ6.4 (Flare Connection) φ6.4 (Flare Connection)
Gas Pipes mm φ12.7 (Flare Connection) φ12.7 (Flare Connection) φ12.7 (Flare Connection)
Drain Pipe mm
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
VP20
(External Dia. 26 Internal Dia. 20)
Machine Weight kg 26 26 26
H5 Sound Level (H/L) dBA 33/29 33/29 33/29
Safety Devices Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor Fuse, Thermal Protector for Fan Motor
Refrigerant Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve
Standard Accessories
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Operation Manual,
Installation Manual, Warranty,
Drain Hose, Sealing Pads, Clamps,
Washers, Insulation for Fitting,
Clamp Metal, Washer Fixing Plate,
Screws for Duct Flanges, Air Filter
Drawing No. 3D045744
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3