Appendix 233
7.1.5 Interlocked Operation with 2 or More Group of VRV System
Purposes and
Functions
When the HRV unit is interlocked to 2 or more group of indoor units, the HRV unit operates,
if one of indoor unit in groups is in operation. The HRV unit can also be operated
independently by remote controller for indoor unit, even if the indoor unit is not in operation.
Cautions: 1. It is not necessary to set the group number for central control.
2. One adapter PCB for remote control should be installed in the one of the unit connected to
the central transmission line.
(When you install an adapter PCB for remote control in the indoor unit, select the applicable
model number of Adapter PCB to be installed.)
Example of
Control Wiring
Note: The central transmission line can be extended up to 1000 m maximum.
Switch Setting for
HRV Unit
The initial setting by the remote controller for indoor unit or HRV unit.
Optional
Accessories
Required
Adapter PCB for remote control: KRP2A61
X9A
X10A
X11A
J1 J2 F1 F2
P1 P2
JC
B1 B2 BC
W1 W2 W3 W4
SS1
F1 F2
P1 P2
P1 P2
F1 F2
P1 P2
P1 P2
F1 F2
P1 P2
P1 P2
Up to 1000 m maximum
Indoor unit
Indoor unit
Indoor unit HRV unit
Remote controller for indoor unit
Remote controller for indoor unit
(HC0027)
KRP2A1
(Installed in
the HRV unit)