Daikin RXYQ14P7W1B [62/80] Ventilation

Daikin RXYQ14P7W1B [62/80] Ventilation
1
Ventilation
p. 62
Total heat exchanged foul air
Foul indoor air
Total heat
exchanged clean air
Clean outdoor air
The Daikin heat recovery ventilation system modulates the
temperature and humidity of incoming fresh air to match
indoor conditions. A balance is thus achieved between
indoor and outdoor ambients, enabling the cooling or
heating load placed on the air conditioning system to be
reduced significantly.
HRV units can be controlled individually or integral with
the air conditioning system (Daikin VRV or Sky Air series).
9 models to choose from
Compact, energy saving ventilation
Specially developed heat exchange element with HEP (High Efficiency Paper)
Easy integration into the VRV system
Connectable to current Daikin control systems :
VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA VAM800FA
VAM1000FA VAM1500FA VAM2000FA
150 250 350 500 650 800 1,000 1,500 2,000
27/28.5 28/29 32/34 33/34.5 34.5/35.5 36/37 36/37 39.5/41.5 40/42.5
69 64 98 98 93 137 157 137 137
74 72 75 74 74 74 75 75 75
58 58 61 58 58 60 61 61 61
64 64 65 62 63 65 66 66 66
269 269 285 285 348 348 348 710 710
760 760 812 812 988 988 988 1,498 1,498
509 509 800 800 852 852 1,140 852 1,140
24 24 33 33 48 48 61 132 158
Ø 100 Ø 150 Ø 150 Ø 200 Ø 200 Ø 250 Ø 250 Ø 350 Ø 350
1~, 50Hz, 220-240V
VENTILATION
Air flow rate m
3
/h
Sound pressure level (max.) (1) dBA
External static pressure (max.) Pa
Temperature exchange efficiency %
Enthalpy exchange efficiency heating %
cooling %
Dimensions H mm
W mm
D mm
Weight kg
Duct diameter mm
Power supply VE
VAM-FA
(1) Sound pressure level is measured in heat exchange mode.
VAM-FA7
HRV-Heat Reclaim Ventilation
1
1602UKEPCEN07-200-artwork.indd 621602UKEPCEN07-200-artwork.indd 62 1/8/07 07:18:071/8/07 07:18:07