SiBE041213E Control Specification
Function and Control 38
3.3.3 Four Way Valve Operation Compensation
Outline At the beginning of the operation as the four way valve is switched, the pressure difference to
activate the four way valve is acquired by having output frequency which is more than a certain
fixed frequency, for a certain fixed time.
Detail Starting Conditions
1. When the compressor starts and the four way valve switches from OFF to ON
2. When the four way valve switches from ON to OFF during operation
3. When the compressor starts after resetting
4. When the compressor starts after the fault of four way valve switching
The lower limit of frequency keeps A Hz for B seconds with any conditions 1 through 4 above.
3.3.4 3-minute Standby
Turning on the compressor is prohibited for 3 minutes after turning it off.
(Except when defrosting.)
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows.
(The function is not activated when defrosting.)
35 class 42 class 50 class
Cooling Heating Cooling Heating Cooling Heating
A (Hz) 68 66 48 54 48
B (seconds) 45 60 70
35 class 42 class 50 class
A (Hz) 48 55 55
B (Hz) 64 70 70
C (Hz) 88 85 85
D (seconds) 240 150 ~ 240 120
E (seconds) 360 180 200
F (seconds) 180 300 470
(sec.)
Time
(R13528)
(Hz)
Frequency
C
B
DEF
A