Daikin EHY2KOMB32AA — руководство по установке и эксплуатации газового котла [27/48]

Daikin EHY2KOMB32AA [27/48] Configuration
7 Configuration
Installation and operation manual
27
EHY2KOMB28+32AA
Daikin Altherma H Hybrid – Gas boiler module
4P538953-1A – 2020.02
Parameter Setting Range Default
settings
Description
Maximum space heating power set ~85% 60% Maximum power in heating. This is a
percentage of the maximum set in
parameter . We strongly recommend
not modifying this setting.
. Maximum capacity space heating
pump
80 The setting is controlled by the heat
pump.
Maximum domestic hot water power
set
(not applicable for Switzerland)
~100% 100% Maximum power in instant domestic
hot water. This is a percentage of the
maximum set in parameter . Because
of the 2-digit display, the highest
displayable value is 99. It is however
possible to set this parameter to 100%
(default setting). We strongly
recommend not modifying this setting.
Minimum supply temperature of the
heat curve
10°C~25°C 25°C Do NOT modify this setting on the
boiler. Use the user interface instead.
. Maximum supply temperature of the
heat curve
30°C~90°C 90°C Do NOT modify this setting on the
boiler. Use the user interface instead.
Minimum outside temperature of the
heat curve
–30°C~10°C –7°C Do NOT modify this setting on the
boiler. Use the user interface instead.
Maximum outside temperature of the
heat curve
15°C~30°C 25°C Do NOT modify this setting on the
boiler. Use the user interface instead.
Space heating pump post purge period 0~15min 0min Changing this setting has no effect on
the operation of the unit.
Space heating pump post purge period
after domestic hot water operation
0~15min 0min Changing this setting has no effect on
the operation of the unit.
Position 3-way valve or electric valve 0~3 0 0=Not inverted
1=Inverted
2 and higher=Not applicable
Booster 0~1 0 Changing this setting has no effect on
the operation of the unit.
Step modulation 0~1 1 0=OFF during space heating
operation
1=ON during space heating
operation
It is recommended not to modify this
setting.
Minimal space heating rpm 23%~50% 30% Adjustment range 23~50%.
It is recommended not to modify this
setting in case of natural gas.
. Minimum capacity space heating pump 40 There is no space heating pump in the
gas boiler. Changing this setting has
no effect.
Minimal domestic hot water rpm
(not applicable for Switzerland)
23%~50% 25% Adjustment range 23~50%
(40=propane).
It is recommended not to modify this
setting in case of natural gas.
. Reversible setting 0~1 0 This setting activates the keep hot
function of the gas boiler. It is only
used with reversible heat pump models
and should NEVER be deactivated. It
MUST be deactivated for heating only
models (set to 0).
0=disabled
1=enabled
Start rpm space heating 50%~99% 50% This is the fan rpm before heating
ignition. It is recommended not to
modify this setting.
. Start rpm domestic hot water
(not applicable for Switzerland)
50%~99% 50% Do not modify this setting.