Specifications ESiEN09-06
10 Specifications
Notes:
Notes (1) European/international technical standard setting the limits for voltage changers, voltage fluctuations and flicker in public low-voltage supply systems for
equipment with rated
75A.
(2) European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with
input current > 16A and
75A per phase.
(3) Short-circuit power.
(4) System impedance.
ELECTRICAL SPECIFICATIONS ERQ125A7W1B ERQ200A7W1B ERQ250A7W1B
- MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth
leakage circuit breaker).
- MSC means the maximum current during start up of the compressor.
- Maximum allowable voltage range variation between phases is 2%.
- RLA is based on following conditions: indoor temperature: 27°CDB/19°CWB, outdoor
temperature: 35°CDB.
- Select wire size based on the value of MCA or TOCA.
- TOCA means the total value of each OC set.
- Voltage range: units are suitable for use on electrical systems where voltage supplied
to unit terminal is not below or above listed range limits.
- FLA means the full load amps of the fan motor.
- In accordance with EN/IEC 61000-3-11
(1)
, respectively EN/IEC 61000-3-12
(2)
, it may
be necessary to consult the distribution network operator to ensure that the equipment
is connected only to a supply with Zsys
(4)
Zmax, respectively Ssc
(3)
minimum Ssc
value.