Daikin EKEQFCBV3 [202/299] Af ahu drain level above limit

Daikin EKEQMCBAV3 [202/299] Af ahu drain level above limit
Troubleshooting by Indication on the Remote Control ESiEN09-06
192 Troubleshooting
3.6
AF
” AHU: Drain Level above Limit
Remote Control
Display
AF
Applicable
Models
AHU
Method of
Malfunction
Detection
Water leakage is detected based on float switch ON/OFF operation while the compressor is in
non-operation.
Malfunction
Decision
Conditions
When the float switch changes from ON to OFF while the compressor is in non-operation.
Supposed
Causes
Humidifier unit (optional accessory) leaking
Defect of drain pipe (upward slope, etc.)
Defect of AHU PC board
Troubleshooting
Caution
Defect of AHU PC board.
Modify the drain piping.
YES
NO
NO
YES
(V2782)
Field drain
piping has a defect
such as upward
sloping.
A
humidifier unit
(optional accessory) is
installed on the
AHU.
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check if the humidifier unit is
leaking.
ESiEN09-06.pdf 200 2/16/2010 4:42:52 PM