Daikin FHC50JEV1K [18/24] Additional charge
![Daikin FHC50JEV1K [18/24] Additional charge](/views2/1784692/page18/bg12.png)
ADDITIONAL CHARGE
SPECIAL PRECAUTIONS WHEN CHARGING UNIT WITH SCROLL COMPRESSORS
The refrigerant is pre-charge in the outdoor unit. If the piping length is less than 7.5m, then additional charge after vacuuming
is not necessary. When the piping length is more than 7.5m, use the table below.
Cooling only
Example:
FDM30JEV1K & RD30JEV1K with 13m piping length, additional piping length is 5.5m. Thus,
Additional charge = 5.5[m] x 55[g/m]
= 302.5[g]
Model Indoor FDM50JEV1K FDM60JEV1K
Outdoor RD50JEY1K RD60JEY1K
Additional charge [g/m] 54 102
Model Indoor FDM20JEV1K FDM25JEV1K FDM30JEV1K FDM40JEV1K FDM40JEV1K
Outdoor RD20JEV1K RD25JEV1K RD30JEV1K RD40JEV1K RD40JEY1K
Additional charge [g/m] 19 38 55 65 65
These precautions are intended for use with Scroll compressors only with R22 and R410A refrigerants but are not applied to
others competitive Scroll compressors.
Scroll compressors have a very high volumetric efÞ ciency and quickly pump a deep vacuum if there is insufÞ cient refrigerant
in the system or if refrigerant is added too slowly. Operation with low suction pressure will quickly lead to very high discharge
temperatures. While this process is happening, the scrolls are not being well lubricated – scrolls depend on the oil mist in the
refrigerant for lubrication. A lack of lubrication leads to high friction between the scroll ß anks and tips and generates additional
heat. The combination of heat of compression and heat from increased friction is concentrated in a small localized discharge
area where temperatures can quickly rise to more than 300°C. These extreme temperatures damage the Scroll spirals and the
orbiting Scroll bearing. This damage can occur in less than one minute especially on larger compressors. Failure may occur
in the Þ rst few hours or the damage done during Þ eld charging may show up some time later. Other typical Þ eld charging
problems include undercharging, overcharging, moisture or air in the system etc. In time each one of these problems can
cause compressor failure.
Minimal equipment is required for Þ eld charging. The minimum equipment required to do a satisfactory job is:-
1. Set of service gauges 4. Vacuum gauge
2. Hoses 5. Scales
3. Vacuum pump 6. Thermometer
The proper refrigerant charge should follow the volume as recommended by manufacturer and recommendation should be
followed by the installer.
1. Charging procedures – Single phase compressors
Evacuate the system to -760mmHg. To reduce evacuation time, use short, large diameter hoses and connect to unrestricted
service ports on the system. Quality of vacuum cannot be determined by time – a reliable vacuum gauge must be used. (etc.
electronic vacuum gauge)
Turn the refrigerant cylinder upside down, purge the charging hose and charge liquid through the liquid line charging port
until refrigerant no longer ß ows or until the correct charge has been weighed in. If additional charge is required start the
system and slowly bleed liquid into the suction side until the system is full.
It recommends charging liquid in a CONTROLLED manner into the suction side until the system is full.
This recommendation does not hold true for reciprocating compressors where liquid charging into the suction side could
cause severe damage.
Carefully monitor the suction and discharge pressures – ensure that the suction pressure does not fall below 25 psig (1.7
bar) at any time during the charging process.
Dip-pipe
Liquid withdrawal
Invert cylinder
without dip-pipe
Содержание
- Installation manual 1
- R22 split series 1
- English 3
- Outline and dimensions 3
- Outline and dimensions 4
- English 5
- Installation manual 6
- Notice 6
- Safety precautions 6
- Warning caution 6
- English 7
- Indoor unit 7
- Installation diagram 7
- Outdoor unit 7
- Installation of the indoor unit 8
- Ceiling concealed drain piping work 9
- English 9
- Caution 10
- Installation of the outdoor unit 10
- All model a b c d 11
- English 11
- Gas pipe size mm in 11
- Installation clearance 11
- Liquid pipe size mm in 11
- Max allowable elevation m 11
- Max allowable length m 11
- Maximum pipe length 11
- Minimum distance mm 300 1000 300 500 11
- Model indoor 11
- Outdoor 11
- Outdoor units must be installed such that there is no short circuit of the hot discharge air or obstruction to smooth air ow select the coolest possible place where intake air should not be hotter than the outside temperature refer to operating range 11
- Refrigerant piping 11
- Remark for fdm60jev1k cooling unit recommended to add 6 kg external accumulator 11
- When the pipe length becomes too long both the capacity and reliability drop as the number of bends increases system piping resistance to the refrigerant ow increases thus lowering the cooling capacity as a result compressor reliability will be affected always choose the shortest path and follow the recommendation as tabulated below 11
- Piping connection to the units 12
- Piping works and flaring technique 12
- Electrical connection 13
- English 13
- English 15
- Charge operation 17
- English 17
- Vacuuming and charging 17
- Vacuuming the piping and the indoor unit 17
- Additional charge 18
- Special precautions when charging unit with scroll compressors 18
- Caution 19
- English 19
- Indicator lights 19
- Operating range 20
- Overall checking 20
- Phase protector optional 20
- Caution 21
- English 21
- Service and maintenance 21
- Troubleshooting 21
Похожие устройства
- Daikin FHC20JEVLK Инструкция по эксплуатации
- Daikin FHC20JEVLK Инструкция по монтажу
- Daikin FHC25JEVLK Инструкция по эксплуатации
- Daikin FHC25JEVLK Инструкция по монтажу
- Daikin FHC30JEVLK Инструкция по эксплуатации
- Daikin FHC30JEVLK Инструкция по монтажу
- Daikin FHC40JEVLK Инструкция по эксплуатации
- Daikin FHC40JEVLK Инструкция по монтажу
- Daikin FHC50JEVLK Инструкция по эксплуатации
- Daikin FHC50JEVLK Инструкция по монтажу
- Daikin FHYC20JEVLK Инструкция по эксплуатации
- Daikin FHYC20JEVLK Инструкция по монтажу
- Daikin FHYC25JEVLK Инструкция по эксплуатации
- Daikin FHYC25JEVLK Инструкция по монтажу
- Daikin FHYC30JEVLK Инструкция по эксплуатации
- Daikin FHYC30JEVLK Инструкция по монтажу
- Daikin FHYC40JEVLK Инструкция по эксплуатации
- Daikin FHYC40JEVLK Инструкция по монтажу
- Daikin FHYC50JEVLK Инструкция по эксплуатации
- Daikin FHYC50JEVLK Инструкция по монтажу