Daikin EHVH04SU18CB6W [100/108] P449983 1 2016 6 1 04 08 _ 2 11 16

Превью страниц Страница 100 / 108
Daikin EHVH08SU18CB6W [100/108] P449983 1 2016 6 1 04 08 _ 2 11 16
4/8
Breadcrumb Field code Setting name Range, step
Default value
Date Value
Field settings table
Installer setting at variance with
default value
└─ Maximum setpoint
A.4.5 [6-0E] R/W 40~65°C, step: 1°C
65°C
└─ SP mode
A.4.6 R/W
0: Fixed
1: Weather de
p
.
└─ Weather dependent curve
A.4.7 [0-0B] Weather-dependent curve Leaving water value for high ambient temp. for
DHW WD curve.
R/W 35~[6-0E]°C, step: 1°C
55°C
A.4.7 [0-0C] Weather-dependent curve Leaving water value for low ambient temp. for
DHW WD curve.
R/W 45~[6-0E]°C, step: 1°C
65°C
A.4.7 [0-0D] Weather-dependent curve High ambient temp. for DHW WD curve. R/W 10~25°C, step: 1°C
15°C
A.4.7 [0-0E] Weather-dependent curve Low ambient temp. for DHW WD curve. R/W -40~5°C, step: 1°C
-10°C
└─ Heat sources
└─ Backup heater
A.5.1.1 [4-00] R/W 0~2
0: Disabled
1: Enabled
A.5.1.3 [4-07] R/W
0: No
1: Yes
A.5.1.4 [5-01] R/W -15~35°C, step: 1°C
0°C
└─ System operation
└─ Auto restart
A.6.1 [3-00] R/W 0: No
1: Yes
└─ Preferential kWh rate
A.6.2.1 [D-00] R/W
0: None
1: BSH only
2: BUH only
3: All heaters
A.6.2.2 [D-05] R/W 0: Forced off
1: As normal
└─ Pwr consumpt. Control
A.6.3.1 [4-08] R/W
0: No limitation
1: Continuous
2: Di
g
ital in
p
uts
A.6.3.2 [4-09] R/W 0: Current
1: Power
A.6.3.3 [5-05] R/W 0~50 A, step: 1 A
50
A
A.6.3.4 [5-09] R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.5.1 [5-05] Amp. limits for DI Limit DI1 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.2 [5-06] Amp. limits for DI Limit DI2 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.3 [5-07] Amp. limits for DI Limit DI3 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.4 [5-08] Amp. limits for DI Limit DI4 R/W 0~50 A, step: 1 A
50
A
A.6.3.6.1 [5-09] kW limits for DI Limit DI1 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.2 [5-0A] kW limits for DI Limit DI2 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.3 [5-0B] kW limits for DI Limit DI3 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.4 [5-0C] kW limits for DI Limit DI4 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.7 [4-01] R/W
0: None
1: BSH
2: BUH
└─ Averaging time
A.6.4 [1-0A] R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─ Ext amb. sensor offset
A.6.5 [2-0B] R/W -5~5°C, step: 0,5°C
0°C
└─ Boiler efficiency
A.6.A [7-05] R/W
0: Very high
1: High
2: Medium
3: Low
4: Ver
y
low
└─ Emergency
A.6.C R/W
0: Manual
1: Automatic
└─ Overview settings
A.8 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
A.8 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
45°C
A.8 [0-02] R/W 10~25°C, step: 1°C
15°C
A.8 [0-03] R/W -40~5°C, step: 1°C
-10°C
A.8 [0-04]
8
A.8 [0-05]
12
A.8 [0-06]
35
A.8 [0-07]
20
A.8 [0-0B] R/W 35~[6-0E]°C, step: 1°C
55°C
A.8 [0-0C] R/W
45~[6-0E]°C, step: 1°C
65°C
A.8 [0-0D] R/W 10~25°C, step: 1°C
15°C
A.8 [0-0E] R/W -40~5°C, step: 1°C
-10°C
--
--
--
Operation mode
Enable BUH step 2
Equilibrium temp.
Allowed heaters
Forced pump OFF
Mode
Type
Amp. value
kW value
Priority
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
--
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
4P449983-1 - 2016.06 (*1) *04/08*_(*2) *11/16*