Daikin EHSX04P30A — installation and Maintenance Guide for Heat Pump Systems [48/68]

Daikin EHSX08P50A [48/68] X errors malfunctions and messages
Installation and maintenance manual
48
Daikin Altherma EHS(X/H)
Daikin Solar tank with integrated interior heat pump unit
008.1420744 – 06/2015
7 x Errors, malfunctions and messages
E9009 AA
STB fault
Optional: STB backup
heater (EKBUxx)
Thermal protection switch (STB) on Backup Heater (EKBUxx) was
triggered.
Replace backup heater (EKBUxx).
E9010 AC Bridge on board A1P
Bridge of connection socket "X21A" missing on board A1P.
Plug in strapping plug.
E9011 C0 Fault flow sensor Flow sensor FLS
Flow sensor FLS defective.
Replace flow sensor FLS.
E9012 C4
Fault feed flow
sensor
Flow temperature sensor
t
V2
or t
V, BH
Measurement outside the permitted value range. Sensor or con-
nection cable defective.
Check, replace.
E9013 E1 OU main board def
Main board of the heat
pump exterior unit
Main board in the heat pump exterior unit defective.
Ventilator motor defective.
Check, replace.
E9014 E3
Coolant over-pres-
sure
High pressure switch
S1PH in the coolant sys
-
tem
Pressure in refrigerant system is too high.
High pressure switch S1PH or ventilator motor defective.
Check, replace.
Poor cable contact.
Flow in the heating system too low.
Filled coolant quantity too high.
Check, replace.
Service valve in the heat pump exterior unit not open.
Service valve open.
E9015 E4
Coolant under-
pressure
Pressure sensor S1NPH
in the heat pump exterior
unit
Pressure in the coolant system is too low.
Coolant quantity too low.
Check, correct cause, refill coolant.
Pressure sensor S1NPH in the heat pump exterior unit defec-
tive.
Temperature sensor lamella heat exchanger R4T in the heat
pump exterior unit defective.
Solenoid valve in the heat pump exterior unit not open.
Main board in the heat pump exterior unit defective.
Check, replace.
E9016 E5 Load protec comp
Electronic overload pro-
tection in the coolant com-
pressor
Coolant compressor overload protection triggered. Pressure dif-
ference between the high and low pressure sides in the coolant
circuit too high (>26
bar).
Coolant compressor defective.
Inverter board in the heat pump exterior unit defective.
Coolant compressor / inverter board cabling, poor contact.
Filled coolant quantity too high.
Check, replace.
Service valve in the heat pump exterior unit not open.
Service valve open.
E9017 E7 Fan blocked
Ventilator motor in the
heat pump exterior unit
A fan in the external heat pump device is blocked.
Check ventilator for the effects of contamination or
blockages, if necessary clean and clear blockage.
Ventilator motor defective.
Ventilator motor, poor contact.
Overvoltage at the ventilator motor.
Fuse in the heat pump exterior unit defective.
Inverter board in the heat pump exterior unit defective.
Check, replace.
E9018 E9 Expansion valve
Electronic expansion
valve
The electronic expansion valve in the external heat pump unit is
defective, replace.
Code Malfunction /
Error message
Component/Designation Causes and possible error correction
Display Internal