Daikin EHSX04P30A [62/68] X technical data

Daikin EHSX04P30A [62/68] X technical data
FLS Sensor (Flow/Temperature)
FLS
(t
R1
/ V1)
V1
Measured flow in l/min
10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0
Sensor output frequency in Hz
(14 - 229 Hz)
28 54 81 108 135 162 188 215
t
R1
Measured temperature in °C
10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0
Sensor resistance in Ohm
(Pt 1000)
1039 1077 1116 1155 1194 1232 1270 1308 1347
Tab. 9-3 Sensor Table Daikin Altherma EHS(X/H)
Maximum tightening torque of sensor =10 Nm.
R
S
Sensor resistance (NTC)
t Temperature
t
DHW2
Storage tank temperature sensor
t
R2
Return flow temperature sensor
t
V1
, t
V2
Flow temperature sensor
t
V, BH
Flow temperature sensor Backup Heater
Fig. 9-1 Characteristics of the NTC temperat
ure sensor Daikin Alther-
ma EHS(X/H) - part 1
t;
AU
t
DHW1
R
S
Sensor resistance (NTC)
t Temperature
t
AU
External temperature sensor RoCon OT1
t
DHW1
Storage tank temperature sensor
Fig. 9-2 Characteristics of the NTC temperat
ure sensor Daikin Alther-
ma EHS(X/H) - Part 2
m / l/min
f Frequency
mFlow
Fig. 9-3 Characteristics of the flow sensor F
LS (V1) Daikin Altherma
EHS(X/H)
R
S
Sensor resistance (Pt 1000))
t Temperature
t
R1
Return flow temperature sensor in the flow meter
Fig. 9-4 Characteristics of the return flow temperature sensor in the
flow sensor F
LS (t
R1
) Daikin Altherma EHS(X/H)
Installation and maintenance manual
62
Daikin Altherma EHS(X/H)
Daikin Solar tank with integrated interior heat pump unit
008.1420744 – 06/2015
9 x Technical data