Operating instructions
12
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
3 x Operation
Operating mode Automatic 2 (Timer programme)
Automatic heating and economy mode in accordance with the
permanent timer programmes (see section 3.4.7):
– [HC Program 2]
– [DHW Program 2]
If, in the active operating mode, the hot water gener-
ation is in setback, you can use the rotary switch
to set temporary "DHW Reheating" without having to
change any other standard settings (see section 3.4.6).
Switching contact for external operating mode
switching
Likewise, the operating mode (see tab. 3-6) can be
switched from an external device (e.g. modem, etc.) via
a potential-free switching contact which is connected to
a resistor and to the terminals "EXT" at the J8 port on
the Daikin Altherma EHS(X/H).
Operating mode Resistance Tolerance
Standby < 680 Ω
± 5 %
Heating 1200 Ω
Reducing 1800 Ω
Summer 2700 Ω
Automatic 1 4700 Ω
Automatic 2 8200 Ω
Tab. 3-6 Resistance values for the evaluation of the EXT signal
The resistances specified in tab. 3-6 work at a toler-
ance range of 5 %. Resistances outside of this toler-
ance ranges are interpreted as open input. The heat
gen
erator resets to the previously active operation
mode.
At resistance values higher than the value for
"Automatic 2", the input is not considered.
If several switching contacts are to be connected to the
Daikin Altherma EHS(X/H) (e.g. SMART GRID, Room
thermostat), the associated functions can have a higher
priority than the external operating mode switching. The
operating mode requested by the EXT switching
contact might then not be activated or may be activated
later.
In addition to these operating modes there are vario
us different
temporary heating programmes available (see tab. 3-7), which
run according to priority after they have been activated.
Temporary timer
programme
Setting /
activating in
level
Rotary
switch
setting
Note
DHW Install DHW Install
Section
3.4.6
Party
Time Program
Section
3.4.7
Away
Holiday
Vacation
Screed*
Configuration >
HC Configu
ration
Section
3.6.13
* Only with expert code.
Tab. 3-7 Overview of temporary timer programmes
If a temporary timer programme (DHW Install, Party,
Away, Holiday, Vacation, Screed) is started during the
selected operating mode, the regulation will take place
with preference according to the settings of this timer
programme.
3.4.3 Temperature setting Daytime room temperature
The set room temperatures for room heating during the day are
determined in the rotary switch setting .
● Place the rotary switch in the "Set Temp Day" position.
An overview is displayed.
The end figures of the parameter designations (1 - 3)
within this rotary switch setting designate the associ-
ation with each individual cycle of the timer
programme.
● Select the temperature block to be set with the rotary switch.
● Confirm the changes with a brief push of the rotary switch.
Settings are displayed.
● Se
t the temperature.
● Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 5.5.
3.4.4 Temperature setting Economy mode
The set room temperatures for room heating in economy mode
are determined in the rotary switch setting
.
● Place the rotary switch in th
e "Set Temp Night" position.
An overview is displayed.
● Sele
ct the parameter to be set with the rotary switch.
● Confirm the changes with a brief push of the rotary switch.
– [T-Reduced]: Set value for "Reducing" operating mode or
setback by a permanent timer programme.
– [T-Absence]: Set value for temporary heating / cooling
prog
rammes ("Away" and "Vacation").
Settings are displayed.
● Se
t the temperature.
● Confirm the changes with a brief push of the rotary switch.
Change has been accepted. Jump back to previous dis-
play.
More detailed explanations and possible setting values for this rotary switch setting
can be seen in chapter 5.6.
Содержание
- Operating instructions p.1
- Daikin control rocon hp ehs157034 ehs157068 p.1
- Special system settings 18 p.2
- Parameter 49 p.2
- Connect the optional rocon devices and start them up 28 p.2
- Special functions 17 p.2
- Other items 50 p.2
- Basic functions and operating modes 9 p.2
- Operation 6 p.2
- Avoid danger 3 p.2
- Safety 3 p.2
- Operating concept 8 p.2
- Rotary switch setting time program 39 p.2
- Observing instructions 3 p.2
- Rotary switch setting set temp night 38 p.2
- Notes 8 p.2
- Rotary switch setting set temp day 38 p.2
- Module 42 p.2
- Rotary switch setting remote param 39 p.2
- Malfunctions and fault codes 46 p.2
- Rotary switch setting operating mode 37 p.2
- Rotary switch setting info 40 5 1 exit button sonderfunktion 41 5 2 parameter level basic configuration 41 5 3 parameter levels for the ehs157068 mixer p.2
- List of keywords 1 p.2
- Rotary switch setting dhw set temp 38 p.2
- List of contents p.2
- Rotary switch setting dhw install 37 p.2
- Initial start up 28 p.2
- Rotary switch setting configuration 31 p.2
- Glossary 7 p.2
- Recognising errors correcting malfunctions 45 p.2
- General 6 p.2
- Warning signs and explanation of symbols 3 p.2
- Proper use 4 p.2
- Explanation of the parameter tables 31 p.2
- User specific settings 48 p.2
- Product description 5 p.2
- Errors malfunctions and messages 5 p.2
- Starting up the daikin altherma ehs x h 28 p.2
- Parameter settings 1 p.2
- Emergency operation 46 p.2
- X safety p.3
- Warning signs and explanation of symbols p.3
- Validity p.3
- Special warning signs p.3
- Safety p.3
- Relevant documents p.3
- Observing instructions p.3
- Meaning of the warnings p.3
- Handling instructions p.3
- Display readouts of the rocon control p.3
- Avoid danger p.3
- X safety p.4
- Proper use p.4
- X product description p.5
- Product description p.5
- X operation p.6
- Operation p.6
- Maximum energy utilisation p.6
- General p.6
- Explanation of symbols p.6
- Display and operating elements p.6
- Display p.6
- X operation p.7
- Rotary switch p.7
- Operating elements p.7
- X operation p.8
- Operating concept p.8
- Exit button p.8
- Button block p.8
- X operation p.9
- System information info p.9
- Display operating data p.9
- Basic functions and operating modes p.9
- Automatic defrosting function p.9
- X operation p.10
- Displaying the water pressure p.10
- X operation p.11
- Setting the operating mode p.11
- Operating modes heating cooling p.11
- Operating mode summer p.11
- Operating mode standby stand by p.11
- Operating mode reducing p.11
- Operating mode automatic 1 timer programme p.11
- Temperature setting daytime room temperature p.12
- Operating mode automatic 2 timer programme p.12
- X operation p.12
- Temperature setting economy mode p.12
- X operation p.13
- Unplanned hot water generation p.13
- Temperature setting hot water generation p.13
- Switching time program p.13
- Permanent timer programmes p.13
- Adjustment p.13
- X operation p.14
- X operation p.15
- Terminal function p.15
- Temporary timer programmes p.15
- System settings p.15
- Setting the language date time p.15
- Assign the terminal address of the daikin altherma ehs x h to the control element rocon b1 p.16
- Activating deactivating normal operation p.16
- X operation p.16
- Smart grid p.16
- Quite mode p.16
- X operation p.17
- Special functions p.17
- Manual operation p.17
- X operation p.18
- Special system settings p.18
- Manually adapting the heating curve p.18
- Heat curve p.18
- Expert p.18
- Caution danger of overheating with underfloor heating p.18
- Access rights technician password p.18
- X operation p.19
- Cooling characteristic curve p.19
- Caution risk of condensation p.19
- X operation p.20
- Weather controlled flow temperature regulation p.20
- If a mixer module is connected p.20
- Frost protection function p.20
- X operation p.21
- Interlink function p.21
- Caution p.21
- Additional heat generator p.21
- X operation p.22
- Special function switching contacts p.22
- Heating support p.22
- Electrical connections to settings 2 and 3 of the parameter function heating rod p.22
- Caution p.22
- X operation p.23
- Legionella protection p.23
- Air purge p.23
- X operation p.24
- Reset to factory settings reset p.24
- Possibility 3 p.24
- Possibility 2 p.24
- Option 1 p.24
- X operation p.25
- Screed program p.25
- Ready to apply heating p.25
- Function heating p.25
- X operation p.26
- Screed program setting and starting p.26
- X operation p.27
- Settings for optional circulation pump p.27
- Setting the timer programme for the circulation pump p.27
- Remote control via internet p.27
- Relay test p.27
- X initial start up p.28
- Starting up the ehs157068 mixer module p.28
- Starting up the daikin altherma ehs x h p.28
- Initial start up p.28
- Connect the optional rocon devices and start them up p.28
- X initial start up p.29
- Starting up the ehs157034 room station p.29
- Procedure for commissioning p.29
- A configuration for setting living room p.29
- X initial start up p.30
- Caretaker function p.30
- B configuration for setting mixing valve p.30
- Rotary switch setting configuration p.31
- Parameter settings p.31
- Level setup p.31
- Explanation of the parameter tables p.31
- X parameter settings p.31
- X parameter settings p.32
- X parameter settings p.33
- Tab 5 1 parameter in rotary switch setting configuration level setup p.33
- X parameter settings p.34
- Level system configuration p.34
- X parameter settings p.35
- Tab 5 2 parameter in rotary switch setting configuration level system configuration p.35
- Level hc configuration p.35
- Depending on the version of the device software certain information parameters for the device not described in tab 5 2 can be displayed at this level for this see tab 5 12 p.35
- X parameter settings p.36
- Tab 5 3 parameter in rotary switch setting configuration level hc configuration p.36
- X parameter settings p.37
- Rotary switch setting operating mode p.37
- Rotary switch setting dhw install p.37
- Level dhw configuration p.37
- X parameter settings p.38
- Tab 5 9 parameter in rotary switch setting dhw set temp p.38
- Tab 5 8 parameter in rotary switch setting set temp night p.38
- Tab 5 7 parameter in rotary switch setting set temp day p.38
- Rotary switch setting set temp night p.38
- Rotary switch setting set temp day p.38
- Rotary switch setting dhw set temp p.38
- X parameter settings p.39
- Tab 5 11 parameter in rotary switch setting remote param p.39
- Tab 5 10 parameter in rotary switch setting time program p.39
- Rotary switch setting time program p.39
- Rotary switch setting remote param p.39
- X parameter settings p.40
- Tab 5 12 parameter in rotary switch setting info p.40
- Rotary switch setting info p.40
- After in the rotary switch position configuration level setup the parameter system config has been set to inac tive or delete p.41
- X parameter settings p.41
- This parameter level appears only if at initial commissioning if the query use standard configura tion is answered by no or p.41
- Tab 5 14 parameter in the level basic configuration p.41
- Tab 5 13 parameter in the level sonderfunktion p.41
- Parameter level basic configuration p.41
- Exit button sonderfunktion p.41
- Rotary switch setting info p.42
- Rotary switch setting dhw set temp p.42
- Rotary switch setting dhw install p.42
- Rotary switch setting configuration level setup p.42
- Rotary switch setting configuration p.42
- X parameter settings p.42
- Parameter levels for the ehs157068 mixer module p.42
- When the assigned control unit is set to living room the t room adj parameter is available the rotary switch can be used to change the room target temperature to the range 5 k to 5 k this function is not available if the control unit is being used as a terminal function for remote control p.42
- No function p.42
- The parameter levels parameter priorities setting ranges and associated functions are essentially the same as those described in the preceding sections p.42
- The description below relates only to the sections indicated areas where there are significant differences are described in greater detail p.42
- Level setup p.42
- See sections 5 3 and 5 3 p.42
- In some cases there exist at individual levels a restricted scope of available parameters p.42
- See section 5 0 p.42
- If the assigned control unit is set to mix valve x the displayed values relate to the assigned heating circuit and to the compo nents connected to the ehs157068 pump mixer valve p.42
- See section 5 p.42
- Rotary switch setting time program p.42
- Rotary switch setting set temp night p.42
- Rotary switch setting set temp day p.42
- Rotary switch setting remote param p.42
- Rotary switch setting operating mode p.42
- X parameter settings p.43
- Rotary switch setting configuration level mixer config p.43
- Rotary switch setting configuration p.43
- Level mixer config p.43
- X parameter settings p.44
- Tab 5 16 parameter in rotary switch setting configuration level mixer config p.44
- X errors malfunctions and messages p.45
- Troubleshooting p.45
- Recognising errors correcting malfunctions p.45
- Read protocol p.45
- Errors malfunctions and messages p.45
- Current fault display p.45
- X errors malfunctions and messages p.46
- Malfunctions and fault codes p.46
- Emergency operation p.46
- X glossary p.47
- Glossary p.47
- X notes p.48
- User specific settings p.48
- Switching time program p.48
- X notes p.49
- Rocon appliance data bus address comments p.49
- Parameter p.49
- Enter your parameter changes in the table below p.49
- Data bus addresses p.49
- Circulation time p.49
- X notes p.50
- Other items p.50
- X list of keywords p.51
- List of keywords p.51
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика
Узнайте, как правильно использовать автоматические режимы отопления и горячего водоснабжения. Подробные инструкции и советы по настройке.