5 x Parameter settings
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
Operating instructions
33
Air Purge Activation of automatic bleeding of the Daikin Altherma EHS(X/H) and the connected
heating circuit (see chapter 3.6.10).
Off: Deactivated
On: Start of Air Purge
N E Off
On
Off -
PWM Config
Max Perform Pump Upper limit for modulation of the pump output N E 20 - 100 % 100 % 1 %
Min Perform Pump Lower limit for modulation of the pump output N E 10 - 100 % 50 % 1 %
Sensor Config
Outside Config Configuration of the optional external temperature sensor RoCon OT1:
Off: No sensor evaluation
On: Sensor evaluation activates (if an outdoor temperature sensor is not connected, a
f
ault message is generated.)
N E Off
On
Off -
Storage Config Configuration of water heating:
inactive; no function for hot water generation.
Sensor: Function for hot water generation is a
ctivated. A circulating tank temperature
sensor is evaluated for hot water generation (if no circulating tank temperature sensor is
connected, a fault message is generated).
Thermostat: Function for hot water generation is activated. A thermostatic switch (On /
O
ff) is evaluated for hot water generation, and where "Open brackets" are evaluated as
"No demand".
N E Inactive
Sensor
Thermostat
Sensor -
Pressure Config Configuring the sensor for assessment of the system water pressure:
Off: No sensor evaluation
On: Sensor evaluation activated (if no pressure se
nsor is connected, a fault message is
generated.)
N E Off
On
On -
Outside Temp Adap Individual adapting for the measured value of the outdoor temperature relevant for the
Con
trol.
N E -5.0 to +5.0 K 0.0 K 0.1 K
Terminaladress Setting the data bus address for system access.
The set value must be applicable for the
entire system. Confirmation of this parameter using the rotary switch reinitialises the con-
troller.
N E Off, 0 - 9 Off 1
System Config System configuration of the unit, consisting of
the sensor configuration and bus configu-
ration. If you answer "Yes" to the enquiry about using the standard configuration when
st
arting the unit for the first time, the basic configuration for the installed heat generator
will be activated automatically.
Confirmation of this parameter setting as "
Inactive" or "Delete" using the rotary switch
reinitialises the controller. A fault message follows. After this the rotary switch must be
set to the position "Info". Use the rotary switch to select the required menu item.
N E Inactive
Active
Delete
Active -
HC Assignment Display only on connected
room station:
Allocation of the room station to the heating circuit to be operated.
The direct heating circuit of the Daikin Alth
erma EHS(X/H) is set as standard to "0"
(see section 5.12, parameter [Unmixed Circ Config])
N E Off, 0 - 15 Off 1
Tab. 5-1 Parameter in rotary switch setting "Configuration" level "Setup"
Sub-
level
Parameter Description Access Setting range
Min / Max
Factory
setting
Increment
BE HF
Содержание
- Operating instructions p.1
- Daikin control rocon hp ehs157034 ehs157068 p.1
- Special system settings 18 p.2
- Parameter 49 p.2
- Connect the optional rocon devices and start them up 28 p.2
- Special functions 17 p.2
- Other items 50 p.2
- Basic functions and operating modes 9 p.2
- Operation 6 p.2
- Avoid danger 3 p.2
- Safety 3 p.2
- Operating concept 8 p.2
- Rotary switch setting time program 39 p.2
- Observing instructions 3 p.2
- Rotary switch setting set temp night 38 p.2
- Notes 8 p.2
- Rotary switch setting set temp day 38 p.2
- Module 42 p.2
- Rotary switch setting remote param 39 p.2
- Malfunctions and fault codes 46 p.2
- Rotary switch setting operating mode 37 p.2
- Rotary switch setting info 40 5 1 exit button sonderfunktion 41 5 2 parameter level basic configuration 41 5 3 parameter levels for the ehs157068 mixer p.2
- List of keywords 1 p.2
- Rotary switch setting dhw set temp 38 p.2
- List of contents p.2
- Rotary switch setting dhw install 37 p.2
- Initial start up 28 p.2
- Rotary switch setting configuration 31 p.2
- Glossary 7 p.2
- Recognising errors correcting malfunctions 45 p.2
- General 6 p.2
- Warning signs and explanation of symbols 3 p.2
- Proper use 4 p.2
- Explanation of the parameter tables 31 p.2
- User specific settings 48 p.2
- Product description 5 p.2
- Errors malfunctions and messages 5 p.2
- Starting up the daikin altherma ehs x h 28 p.2
- Parameter settings 1 p.2
- Emergency operation 46 p.2
- X safety p.3
- Warning signs and explanation of symbols p.3
- Validity p.3
- Special warning signs p.3
- Safety p.3
- Relevant documents p.3
- Observing instructions p.3
- Meaning of the warnings p.3
- Handling instructions p.3
- Display readouts of the rocon control p.3
- Avoid danger p.3
- X safety p.4
- Proper use p.4
- X product description p.5
- Product description p.5
- X operation p.6
- Operation p.6
- Maximum energy utilisation p.6
- General p.6
- Explanation of symbols p.6
- Display and operating elements p.6
- Display p.6
- X operation p.7
- Rotary switch p.7
- Operating elements p.7
- X operation p.8
- Operating concept p.8
- Exit button p.8
- Button block p.8
- X operation p.9
- System information info p.9
- Display operating data p.9
- Basic functions and operating modes p.9
- Automatic defrosting function p.9
- X operation p.10
- Displaying the water pressure p.10
- X operation p.11
- Setting the operating mode p.11
- Operating modes heating cooling p.11
- Operating mode summer p.11
- Operating mode standby stand by p.11
- Operating mode reducing p.11
- Operating mode automatic 1 timer programme p.11
- Temperature setting daytime room temperature p.12
- Operating mode automatic 2 timer programme p.12
- X operation p.12
- Temperature setting economy mode p.12
- X operation p.13
- Unplanned hot water generation p.13
- Temperature setting hot water generation p.13
- Switching time program p.13
- Permanent timer programmes p.13
- Adjustment p.13
- X operation p.14
- X operation p.15
- Terminal function p.15
- Temporary timer programmes p.15
- System settings p.15
- Setting the language date time p.15
- Assign the terminal address of the daikin altherma ehs x h to the control element rocon b1 p.16
- Activating deactivating normal operation p.16
- X operation p.16
- Smart grid p.16
- Quite mode p.16
- X operation p.17
- Special functions p.17
- Manual operation p.17
- X operation p.18
- Special system settings p.18
- Manually adapting the heating curve p.18
- Heat curve p.18
- Expert p.18
- Caution danger of overheating with underfloor heating p.18
- Access rights technician password p.18
- X operation p.19
- Cooling characteristic curve p.19
- Caution risk of condensation p.19
- X operation p.20
- Weather controlled flow temperature regulation p.20
- If a mixer module is connected p.20
- Frost protection function p.20
- X operation p.21
- Interlink function p.21
- Caution p.21
- Additional heat generator p.21
- X operation p.22
- Special function switching contacts p.22
- Heating support p.22
- Electrical connections to settings 2 and 3 of the parameter function heating rod p.22
- Caution p.22
- X operation p.23
- Legionella protection p.23
- Air purge p.23
- X operation p.24
- Reset to factory settings reset p.24
- Possibility 3 p.24
- Possibility 2 p.24
- Option 1 p.24
- X operation p.25
- Screed program p.25
- Ready to apply heating p.25
- Function heating p.25
- X operation p.26
- Screed program setting and starting p.26
- X operation p.27
- Settings for optional circulation pump p.27
- Setting the timer programme for the circulation pump p.27
- Remote control via internet p.27
- Relay test p.27
- X initial start up p.28
- Starting up the ehs157068 mixer module p.28
- Starting up the daikin altherma ehs x h p.28
- Initial start up p.28
- Connect the optional rocon devices and start them up p.28
- X initial start up p.29
- Starting up the ehs157034 room station p.29
- Procedure for commissioning p.29
- A configuration for setting living room p.29
- X initial start up p.30
- Caretaker function p.30
- B configuration for setting mixing valve p.30
- Rotary switch setting configuration p.31
- Parameter settings p.31
- Level setup p.31
- Explanation of the parameter tables p.31
- X parameter settings p.31
- X parameter settings p.32
- X parameter settings p.33
- Tab 5 1 parameter in rotary switch setting configuration level setup p.33
- X parameter settings p.34
- Level system configuration p.34
- X parameter settings p.35
- Tab 5 2 parameter in rotary switch setting configuration level system configuration p.35
- Level hc configuration p.35
- Depending on the version of the device software certain information parameters for the device not described in tab 5 2 can be displayed at this level for this see tab 5 12 p.35
- X parameter settings p.36
- Tab 5 3 parameter in rotary switch setting configuration level hc configuration p.36
- X parameter settings p.37
- Rotary switch setting operating mode p.37
- Rotary switch setting dhw install p.37
- Level dhw configuration p.37
- X parameter settings p.38
- Tab 5 9 parameter in rotary switch setting dhw set temp p.38
- Tab 5 8 parameter in rotary switch setting set temp night p.38
- Tab 5 7 parameter in rotary switch setting set temp day p.38
- Rotary switch setting set temp night p.38
- Rotary switch setting set temp day p.38
- Rotary switch setting dhw set temp p.38
- X parameter settings p.39
- Tab 5 11 parameter in rotary switch setting remote param p.39
- Tab 5 10 parameter in rotary switch setting time program p.39
- Rotary switch setting time program p.39
- Rotary switch setting remote param p.39
- X parameter settings p.40
- Tab 5 12 parameter in rotary switch setting info p.40
- Rotary switch setting info p.40
- After in the rotary switch position configuration level setup the parameter system config has been set to inac tive or delete p.41
- X parameter settings p.41
- This parameter level appears only if at initial commissioning if the query use standard configura tion is answered by no or p.41
- Tab 5 14 parameter in the level basic configuration p.41
- Tab 5 13 parameter in the level sonderfunktion p.41
- Parameter level basic configuration p.41
- Exit button sonderfunktion p.41
- Rotary switch setting info p.42
- Rotary switch setting dhw set temp p.42
- Rotary switch setting dhw install p.42
- Rotary switch setting configuration level setup p.42
- Rotary switch setting configuration p.42
- X parameter settings p.42
- Parameter levels for the ehs157068 mixer module p.42
- When the assigned control unit is set to living room the t room adj parameter is available the rotary switch can be used to change the room target temperature to the range 5 k to 5 k this function is not available if the control unit is being used as a terminal function for remote control p.42
- No function p.42
- The parameter levels parameter priorities setting ranges and associated functions are essentially the same as those described in the preceding sections p.42
- The description below relates only to the sections indicated areas where there are significant differences are described in greater detail p.42
- Level setup p.42
- See sections 5 3 and 5 3 p.42
- In some cases there exist at individual levels a restricted scope of available parameters p.42
- See section 5 0 p.42
- If the assigned control unit is set to mix valve x the displayed values relate to the assigned heating circuit and to the compo nents connected to the ehs157068 pump mixer valve p.42
- See section 5 p.42
- Rotary switch setting time program p.42
- Rotary switch setting set temp night p.42
- Rotary switch setting set temp day p.42
- Rotary switch setting remote param p.42
- Rotary switch setting operating mode p.42
- X parameter settings p.43
- Rotary switch setting configuration level mixer config p.43
- Rotary switch setting configuration p.43
- Level mixer config p.43
- X parameter settings p.44
- Tab 5 16 parameter in rotary switch setting configuration level mixer config p.44
- X errors malfunctions and messages p.45
- Troubleshooting p.45
- Recognising errors correcting malfunctions p.45
- Read protocol p.45
- Errors malfunctions and messages p.45
- Current fault display p.45
- X errors malfunctions and messages p.46
- Malfunctions and fault codes p.46
- Emergency operation p.46
- X glossary p.47
- Glossary p.47
- X notes p.48
- User specific settings p.48
- Switching time program p.48
- X notes p.49
- Rocon appliance data bus address comments p.49
- Parameter p.49
- Enter your parameter changes in the table below p.49
- Data bus addresses p.49
- Circulation time p.49
- X notes p.50
- Other items p.50
- X list of keywords p.51
- List of keywords p.51
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика
Изучите настройки параметров для систем отопления, включая автоматическое удаление воздуха, конфигурацию датчиков и управление насосами. Оптимизируйте работу вашего оборудования.