5 x Parameter settings
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
Operating instructions
33
Air Purge Activation of automatic bleeding of the Daikin Altherma EHS(X/H) and the connected
heating circuit (see chapter 3.6.10).
Off: Deactivated
On: Start of Air Purge
N E Off
On
Off -
PWM Config
Max Perform Pump Upper limit for modulation of the pump output N E 20 - 100 % 100 % 1 %
Min Perform Pump Lower limit for modulation of the pump output N E 10 - 100 % 50 % 1 %
Sensor Config
Outside Config Configuration of the optional external temperature sensor RoCon OT1:
Off: No sensor evaluation
On: Sensor evaluation activates (if an outdoor temperature sensor is not connected, a
f
ault message is generated.)
N E Off
On
Off -
Storage Config Configuration of water heating:
inactive; no function for hot water generation.
Sensor: Function for hot water generation is a
ctivated. A circulating tank temperature
sensor is evaluated for hot water generation (if no circulating tank temperature sensor is
connected, a fault message is generated).
Thermostat: Function for hot water generation is activated. A thermostatic switch (On /
O
ff) is evaluated for hot water generation, and where "Open brackets" are evaluated as
"No demand".
N E Inactive
Sensor
Thermostat
Sensor -
Pressure Config Configuring the sensor for assessment of the system water pressure:
Off: No sensor evaluation
On: Sensor evaluation activated (if no pressure se
nsor is connected, a fault message is
generated.)
N E Off
On
On -
Outside Temp Adap Individual adapting for the measured value of the outdoor temperature relevant for the
Con
trol.
N E -5.0 to +5.0 K 0.0 K 0.1 K
Terminaladress Setting the data bus address for system access.
The set value must be applicable for the
entire system. Confirmation of this parameter using the rotary switch reinitialises the con-
troller.
N E Off, 0 - 9 Off 1
System Config System configuration of the unit, consisting of
the sensor configuration and bus configu-
ration. If you answer "Yes" to the enquiry about using the standard configuration when
st
arting the unit for the first time, the basic configuration for the installed heat generator
will be activated automatically.
Confirmation of this parameter setting as "
Inactive" or "Delete" using the rotary switch
reinitialises the controller. A fault message follows. After this the rotary switch must be
set to the position "Info". Use the rotary switch to select the required menu item.
N E Inactive
Active
Delete
Active -
HC Assignment Display only on connected
room station:
Allocation of the room station to the heating circuit to be operated.
The direct heating circuit of the Daikin Alth
erma EHS(X/H) is set as standard to "0"
(see section 5.12, parameter [Unmixed Circ Config])
N E Off, 0 - 15 Off 1
Tab. 5-1 Parameter in rotary switch setting "Configuration" level "Setup"
Sub-
level
Parameter Description Access Setting range
Min / Max
Factory
setting
Increment
BE HF