Daikin EHSH16P50A — operating Instructions for Control Systems and Heating Configuration [18/52]
![Daikin EHSH16P50A [18/52] Heat curve](/views2/1786266/page18/bg12.png)
Operating instructions
18
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
3 x Operation
3.6 Special system settings
The Control RoCon HP already has the basic configuration for
the Daikin Altherma EHS(X/H). However, it needs to be adapted
to the optionally connected accessories and the installation envi-
ronment during initial commissioning.
Adaptation is carried out via the setting of parameters in the
rotary switch se
tting "Configuration" .
Navigating with the rotary switch accesses either the next deeper
level or directly to the appropriate parameter.
3.6.1 Access Rights (Technician password)
Certain settings are restricted by Control access rights. In order
to gain access to these setting values (parameters) you need to
enter the expert "Setup" code in the level.
The fig. 3-12 shows the fundamental proced
ure for entering the
access code. The expert code will be advised to the expert
company in a separate letter.
Configuration
Setup
System Configuration
Access Rights
User
Access Rights
Expert
Setup
Language
Date
Setup
Keylock Function
Access Rights
Outdoor type
Access Rights Access Rights
Access Rights
Fig. 3-12 Entering the access code
3.6.2 Heat curve
Caution - danger of overheating with
underfloor heating!
In the event of a fault, or in hand mode, damage may
be caused to the screed, the structure of the floor and
the underfloor heating system by overheating.
● Before initial commissioning of the underfloor
heating system, set the maximum permissible
system temperature Control RoCon HP
(parameter [T vbh1 max]) in the maximum temper-
ature limit in the Control Ro
Con HP (parameter
[Max T-Flow]).
● Conn
ect the overheat protection switch (customer)
on the "EXT" plug connection to the external
operating mode switch so that the Daikin Altherma
EHS(X/H) is in operating mode "Standby" or
"Summer" (see section 3.4.2).
In parameter [Room thermo
stat] = On or parame-
ter [Interlink fct] = On, the overheat protection
switch must be connected so that the switching
contact of the room thermostat is interrupted.
● If th
e underfloor heating system is also used for
room cooling, the connection notes from the
previous section are also valid for the connection
of a customer-provided humidity protection switch.
With the heating characteristic curve, the inflow target temper-
ature is adjusted to building condition
s in accordance with the rel-
evant external temperature (weath
er-controlled flow temperature
regulation, see section 3.6.4). Generally speaking, the steepness
of the heating characteristics describes the ratio of the flow tem-
perature change to the external temperature change.
The heating characteristic curve applies within the minimum and
maximum temperature limits that have been set for the corre-
sponding heating circuit. The room tempera
ture measured in the
living area may differ from the desired room temperature; these
deviations can be kept to a minimum by installing a room station
or a room thermostat.
The Control is set
in the factory so that the heating curve does
not adjust itself during operation.
The automatic heat curve adaptation can be activated (pa-
rameter [HC Adaption]) if the room station (EHS157034) is con-
nected (see chap
ter 3.6.4).
Starting conditions for the automatic hea
ting curve adjustment:
– Outdoor temperature < 8 °C
– Operating mode is automat
ic (I or II)
– Duration of setback phase at least 6 hours
If an
automatic heat curve adjustment is not activated, the heat
curve can be set manually by adjusting the parameter [Heat-
Slope].
Manually adapting the heating curve
Do not make any corrections to the set values for 1 - 2
days, and then only make them in small increments.
● Deactivate additional heat sources (e.g. fireplaces,
direct solar radiation, open windows).
● Fu
lly open any existing radiator thermostat valves
or setting drives.
● Activa
te the operating mode "Heating".
Approximate setting values:
– Radiator: 1.4 to 1.6.
– Underfloor heating system: 0.5 to 0.9.
Содержание
- Operating instructions p.1
- Daikin control rocon hp ehs157034 ehs157068 p.1
- Special system settings 18 p.2
- Parameter 49 p.2
- Connect the optional rocon devices and start them up 28 p.2
- Special functions 17 p.2
- Other items 50 p.2
- Basic functions and operating modes 9 p.2
- Operation 6 p.2
- Avoid danger 3 p.2
- Safety 3 p.2
- Operating concept 8 p.2
- Rotary switch setting time program 39 p.2
- Observing instructions 3 p.2
- Rotary switch setting set temp night 38 p.2
- Notes 8 p.2
- Rotary switch setting set temp day 38 p.2
- Module 42 p.2
- Rotary switch setting remote param 39 p.2
- Malfunctions and fault codes 46 p.2
- Rotary switch setting operating mode 37 p.2
- Rotary switch setting info 40 5 1 exit button sonderfunktion 41 5 2 parameter level basic configuration 41 5 3 parameter levels for the ehs157068 mixer p.2
- List of keywords 1 p.2
- Rotary switch setting dhw set temp 38 p.2
- List of contents p.2
- Rotary switch setting dhw install 37 p.2
- Initial start up 28 p.2
- Rotary switch setting configuration 31 p.2
- Glossary 7 p.2
- Recognising errors correcting malfunctions 45 p.2
- General 6 p.2
- Warning signs and explanation of symbols 3 p.2
- Proper use 4 p.2
- Explanation of the parameter tables 31 p.2
- User specific settings 48 p.2
- Product description 5 p.2
- Errors malfunctions and messages 5 p.2
- Starting up the daikin altherma ehs x h 28 p.2
- Parameter settings 1 p.2
- Emergency operation 46 p.2
- X safety p.3
- Warning signs and explanation of symbols p.3
- Validity p.3
- Special warning signs p.3
- Safety p.3
- Relevant documents p.3
- Observing instructions p.3
- Meaning of the warnings p.3
- Handling instructions p.3
- Display readouts of the rocon control p.3
- Avoid danger p.3
- X safety p.4
- Proper use p.4
- X product description p.5
- Product description p.5
- X operation p.6
- Operation p.6
- Maximum energy utilisation p.6
- General p.6
- Explanation of symbols p.6
- Display and operating elements p.6
- Display p.6
- X operation p.7
- Rotary switch p.7
- Operating elements p.7
- X operation p.8
- Operating concept p.8
- Exit button p.8
- Button block p.8
- X operation p.9
- System information info p.9
- Display operating data p.9
- Basic functions and operating modes p.9
- Automatic defrosting function p.9
- X operation p.10
- Displaying the water pressure p.10
- X operation p.11
- Setting the operating mode p.11
- Operating modes heating cooling p.11
- Operating mode summer p.11
- Operating mode standby stand by p.11
- Operating mode reducing p.11
- Operating mode automatic 1 timer programme p.11
- Temperature setting daytime room temperature p.12
- Operating mode automatic 2 timer programme p.12
- X operation p.12
- Temperature setting economy mode p.12
- X operation p.13
- Unplanned hot water generation p.13
- Temperature setting hot water generation p.13
- Switching time program p.13
- Permanent timer programmes p.13
- Adjustment p.13
- X operation p.14
- X operation p.15
- Terminal function p.15
- Temporary timer programmes p.15
- System settings p.15
- Setting the language date time p.15
- Assign the terminal address of the daikin altherma ehs x h to the control element rocon b1 p.16
- Activating deactivating normal operation p.16
- X operation p.16
- Smart grid p.16
- Quite mode p.16
- X operation p.17
- Special functions p.17
- Manual operation p.17
- X operation p.18
- Special system settings p.18
- Manually adapting the heating curve p.18
- Heat curve p.18
- Expert p.18
- Caution danger of overheating with underfloor heating p.18
- Access rights technician password p.18
- X operation p.19
- Cooling characteristic curve p.19
- Caution risk of condensation p.19
- X operation p.20
- Weather controlled flow temperature regulation p.20
- If a mixer module is connected p.20
- Frost protection function p.20
- X operation p.21
- Interlink function p.21
- Caution p.21
- Additional heat generator p.21
- X operation p.22
- Special function switching contacts p.22
- Heating support p.22
- Electrical connections to settings 2 and 3 of the parameter function heating rod p.22
- Caution p.22
- X operation p.23
- Legionella protection p.23
- Air purge p.23
- X operation p.24
- Reset to factory settings reset p.24
- Possibility 3 p.24
- Possibility 2 p.24
- Option 1 p.24
- X operation p.25
- Screed program p.25
- Ready to apply heating p.25
- Function heating p.25
- X operation p.26
- Screed program setting and starting p.26
- X operation p.27
- Settings for optional circulation pump p.27
- Setting the timer programme for the circulation pump p.27
- Remote control via internet p.27
- Relay test p.27
- X initial start up p.28
- Starting up the ehs157068 mixer module p.28
- Starting up the daikin altherma ehs x h p.28
- Initial start up p.28
- Connect the optional rocon devices and start them up p.28
- X initial start up p.29
- Starting up the ehs157034 room station p.29
- Procedure for commissioning p.29
- A configuration for setting living room p.29
- X initial start up p.30
- Caretaker function p.30
- B configuration for setting mixing valve p.30
- Rotary switch setting configuration p.31
- Parameter settings p.31
- Level setup p.31
- Explanation of the parameter tables p.31
- X parameter settings p.31
- X parameter settings p.32
- X parameter settings p.33
- Tab 5 1 parameter in rotary switch setting configuration level setup p.33
- X parameter settings p.34
- Level system configuration p.34
- X parameter settings p.35
- Tab 5 2 parameter in rotary switch setting configuration level system configuration p.35
- Level hc configuration p.35
- Depending on the version of the device software certain information parameters for the device not described in tab 5 2 can be displayed at this level for this see tab 5 12 p.35
- X parameter settings p.36
- Tab 5 3 parameter in rotary switch setting configuration level hc configuration p.36
- X parameter settings p.37
- Rotary switch setting operating mode p.37
- Rotary switch setting dhw install p.37
- Level dhw configuration p.37
- X parameter settings p.38
- Tab 5 9 parameter in rotary switch setting dhw set temp p.38
- Tab 5 8 parameter in rotary switch setting set temp night p.38
- Tab 5 7 parameter in rotary switch setting set temp day p.38
- Rotary switch setting set temp night p.38
- Rotary switch setting set temp day p.38
- Rotary switch setting dhw set temp p.38
- X parameter settings p.39
- Tab 5 11 parameter in rotary switch setting remote param p.39
- Tab 5 10 parameter in rotary switch setting time program p.39
- Rotary switch setting time program p.39
- Rotary switch setting remote param p.39
- X parameter settings p.40
- Tab 5 12 parameter in rotary switch setting info p.40
- Rotary switch setting info p.40
- After in the rotary switch position configuration level setup the parameter system config has been set to inac tive or delete p.41
- X parameter settings p.41
- This parameter level appears only if at initial commissioning if the query use standard configura tion is answered by no or p.41
- Tab 5 14 parameter in the level basic configuration p.41
- Tab 5 13 parameter in the level sonderfunktion p.41
- Parameter level basic configuration p.41
- Exit button sonderfunktion p.41
- Rotary switch setting info p.42
- Rotary switch setting dhw set temp p.42
- Rotary switch setting dhw install p.42
- Rotary switch setting configuration level setup p.42
- Rotary switch setting configuration p.42
- X parameter settings p.42
- Parameter levels for the ehs157068 mixer module p.42
- When the assigned control unit is set to living room the t room adj parameter is available the rotary switch can be used to change the room target temperature to the range 5 k to 5 k this function is not available if the control unit is being used as a terminal function for remote control p.42
- No function p.42
- The parameter levels parameter priorities setting ranges and associated functions are essentially the same as those described in the preceding sections p.42
- The description below relates only to the sections indicated areas where there are significant differences are described in greater detail p.42
- Level setup p.42
- See sections 5 3 and 5 3 p.42
- In some cases there exist at individual levels a restricted scope of available parameters p.42
- See section 5 0 p.42
- If the assigned control unit is set to mix valve x the displayed values relate to the assigned heating circuit and to the compo nents connected to the ehs157068 pump mixer valve p.42
- See section 5 p.42
- Rotary switch setting time program p.42
- Rotary switch setting set temp night p.42
- Rotary switch setting set temp day p.42
- Rotary switch setting remote param p.42
- Rotary switch setting operating mode p.42
- X parameter settings p.43
- Rotary switch setting configuration level mixer config p.43
- Rotary switch setting configuration p.43
- Level mixer config p.43
- X parameter settings p.44
- Tab 5 16 parameter in rotary switch setting configuration level mixer config p.44
- X errors malfunctions and messages p.45
- Troubleshooting p.45
- Recognising errors correcting malfunctions p.45
- Read protocol p.45
- Errors malfunctions and messages p.45
- Current fault display p.45
- X errors malfunctions and messages p.46
- Malfunctions and fault codes p.46
- Emergency operation p.46
- X glossary p.47
- Glossary p.47
- X notes p.48
- User specific settings p.48
- Switching time program p.48
- X notes p.49
- Rocon appliance data bus address comments p.49
- Parameter p.49
- Enter your parameter changes in the table below p.49
- Data bus addresses p.49
- Circulation time p.49
- X notes p.50
- Other items p.50
- X list of keywords p.51
- List of keywords p.51
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -