Daikin EHSH16P50A — настройки параметров управления отоплением и горячей водой [39/52]

Daikin EHSH08P30A [39/52] Rotary switch setting time program
5 x Parameter settings
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
Operating instructions
39
5.8 Rotary switch setting: Time Program
Parameter Designation Access Setting range
Min / Max
Factory
setting
Increment
BE HF
Party The heating circuit operates at the target room t
emperature set in the [T-Room 1 Setpoint] pa-
rameter for the set period of time. If the [Automatic 1] or [Automatic 2] timer programmes are
a
ctive, the heating cycle is extended or started early. (Target room temperature - see
chapter 3.4.7).
The hot water generation is not affected.
E E 00:00 - 06:00 00:00 1 h
Away The heating circuit operates at the target room temperature set in the [T-Absence] parameter
f
or the set period of time.
The hot water generation is not affected.
E E 00:00 - 06:00 00:00 1 h
Vacation The heating circuit operates at the target room temperature set in the [T-Absence] parameter
p
ermanently (24 h per day).
A calendar function can be used to ente
r a time period for the absence.
E E Date on first
da
y
-
Date on last
day:
- 1 day
Holiday A calendar function can be used to enter a time period for presence.
During this time, the system operates exclusively in accordance with the "Sunday" settings in
[
DHW Program 1] and [HC Program 1].
E E Date on first
da
y
-
Date on last
day:
- 1 day
HC Program 1 In this menu we can parametrise the 1st timer progr
amme for the heating circuit. 3 switching
cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is possi-
ble. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Frida
y, Saturday to Sunday and Monday
to Sunday.
E E See
chapter 3.4.7
See
tab. 3-9
15 min
HC Program 2 In this menu we can parametrise the 2nd. timer pr
ogramme for the heating circuit. 3 switching
cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is possi-
ble. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Frida
y, Saturday to Sunday and Monday
to Sunday.
E E See
chapter 3.4.7
See
tab. 3-9
15 min
DHW Program 1 In this menu we can parametrise the 1st timer programme for hot water generation. 3 switching
cycles wit
h a resolution of 15 minutes can be set. A separate entry for each weekday is possi-
ble. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Frida
y, Saturday to Sunday and Monday
to Sunday.
E E See
chapter 3.4.7
See
tab. 3-9
15 min
DHW Program 2 In this menu we can parametrise the 2nd. timer programme for hot water generation. 3 switch-
ing cycles with a resolution of 15 minutes can be set
. A separate entry for each weekday is
possible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Frida
y, Saturday to Sunday and Monday
to Sunday.
E E See
chapter 3.4.7
See
tab. 3-9
15 min
Circulation Time In this menu we can parametrise a timer programme for
the circulation pump. 3 switching cy-
cles with a resolution of 15 minutes can be set. A
separate entry for each weekday is possible.
Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Frida
y, Saturday to Sunday and Monday
to Sunday.
E E See
chapter 3.4.7
See
tab. 3-9
15
min
Tab. 5-10 Parameter in rotary switch setting "Time Program"
5.9 Rotary switch setting: Remote Param
Parameter Description Access Setting range
Min / Max
Factory
setting
Increment
BE HF
Bus - Scan Off: No function
On: Control checks which RoCon devices are co
nnected to the system using the CAN bus
lines. Devices that are detected are displayed with their type and data bus address (for exam-
ple: MM#8 = mixer module with data bus address 8).
The selection and activation of a device with the rotary switch switches the function of the con-
trol unit to that of the selected device (see chapter 3.4.9).
E E Off
On
Off -
No selection Activation switches to the local device. E E
-
Contr BM1/BE1 #X Activation switches to the Daikin Altherma EHS(X/H) with the bus ID X (see section 5.12, pa-
rameter [BUS ID HS]).
E E
-
Mix Valve #X Activation switches to the mixer module with the bus ID X (see section 5.13.1, parameter
[HC Assignment]).
E E
-
Tab. 5-11 Parameter in rotary switch setting "Remote Param"