Daikin RKHBRD014ADV1 [12/24] When setback function is enabled the setback operation will have priority over the scheduled action in the schedule timer if on instruction is active if off instruction is active this will have priority over the setback function at any time the off instruction will have the highest priority
![Daikin RKHBRD014ADV1 [12/24] When setback function is enabled the setback operation will have priority over the scheduled action in the schedule timer if on instruction is active if off instruction is active this will have priority over the setback function at any time the off instruction will have the highest priority](/views2/1797485/page12/bgc.png)
Operation manual
11
RKHBRD011~016ADV1+Y1
Indoor unit for air to water heat pump system and options
4P403582-1 – 2015.04
Operation example: Schedule timer based on temperature set
points.
When setback function is enabled, the setback operation will have
priority over the scheduled action in the schedule timer.
Operation example: Schedule timer based on ON/OFF instruction.
When setback function is enabled, the setback operation will have
priority over the scheduled action in the schedule timer if ON
instruction is active. If OFF instruction is active this will have priority
over the setback function. At any time the OFF instruction will have
the highest priority.
1 Schedule timer
2 Setback function
3 When both setback function and schedule timer are enabled
A Setback function
t Time
T Temperature set point
Room temperature
Leaving water temperature
Method 2
[0-03]=0
Space heating based on ON/OFF instruction
During operation When the schedule timer switches space heating OFF,
the controller will be switched off (operation LED will stop
working). Note that this has no influence on the domestic
water heating.
When pushing
the button
The schedule timer for space heating will stop (when
active at that moment) and will start again at the next
scheduled ON function.
The "last" programmed command overrules the
"preceding" programmed command and will remain
active until the "next" programmed command occurs.
Example: imagine the actual time is 17:30 and actions
are programmed at 13:00, 16:00 and 19:00. The "last"
programmed command (16:00) overruled the
"previous" programmed command (13:00) and will
remain active until the "next" programmed command
(19:00) occurs.
So in order to know the actual setting, one should consult
the last programmed command. It is clear that the "last"
programmed command may date from the day before.
Refer to "Consulting programmed actions" on page 14.
The controller will be switched off (operation LED will
stop working).
However the schedule timer icon will stay displayed
which means that the domestic heating stays enabled.
When pushing
the / button
The schedule timer for space heating and domestic
water heating along with the quiet mode will be stopped
and will not start again.
The schedule timer icon will not be displayed anymore.
T
t
6:30 9:00
16:00
0:30
19
19
°C 19
19
°C 19
19
°C
22
22
°C
21
21
°C
62
62
°C 62
62
°C 62
62
°C
65
65
°C
64
64
°C
62°C
19°C19°C19°C
22°C
21°C
62°C62°C
65°C
64°C
0:30
1
T
t
18
18
°C
57
57
°C57°C
18°C
A
5:00
5:00
23:00
23:00
5:0023:00
2
T
t
5:00 9:00
16:00
23:00
19
19
°C
18
18
°C
19
19
°C
22
22
°C
21
21
°C
62
62
°C
60
60
°C
62
62
°C
65
65
°C
64
64
°C
60°C
19°C
18°C
19°C
22°C
21°C
62°C62°C
19
19
°C
62
62
°C
19°C
62°C
19
19
°C
62
62
°C
19°C
62°C
19
19
°C
62
62
°C
19°C
62°C
65°C
64°C
6:30
3
57
57
°C57°C
60
60
°C60°C
1 Schedule timer
2 Setback function
3 When both setback function and schedule timer are enabled
A Setback function
B ON/OFF instruction
t Time
T Temperature set point
Room temperature
Leaving water temperature
t
18
18
°C
60
60
°C60°C
18°C
A
5:00
5:00
23:00
23:00
5:0023:00
2
B
t
9:00
16:00
19
19
°C 19
19
°C
22
22
°C
21
21
°C
62
62
°C 62
62
°C
65
65
°C
64
64
°C
19°C19°C
22°C
21°C
62°C62°C
65°C
64°C
1
OFF ONON
6:300:30
B
t
6:30 9:00
16:00
23:00
19
19
°C 19
19
°C
22
22
°C
21
21
°C
62
62
°C 62
62
°C
65
65
°C
64
64
°C
19°C19°C
22°C
21°C
62°C62°C
65°C
64°C
3
OFF ONON
18
18
°C
60
60
°C60°C
18°C
Содержание
- Operation manual p.1
- Indoor unit for air to water heat pump system and options p.1
- Scope of this manual p.2
- Operation manual p.2
- Introduction p.2
- General information p.2
- Domestic water heating operation p.3
- Space heating operation p.3
- Quick start up of the unit p.3
- Peration p.3
- Operation of the unit p.3
- Remote controller buttons and icons p.4
- Setting the clock p.5
- Space heating operation h p.6
- Space heating operation p.6
- Room temperature control p.6
- Leaving water temperature control p.6
- Domestic water heating operation w p.8
- Domestic water heating operation p.8
- Automatic storage p.8
- Manual storage p.9
- Defrost operation d p.10
- Defrost operation p.10
- Start up operation d p.10
- Start up operation p.10
- Reheat p.10
- Quiet mode operation s p.10
- Quiet mode operation p.10
- Other operation modes p.10
- Emergency operation p.10
- Disinfection operation p.10
- Temperature read out mode p.11
- Space heating p.11
- Simultaneous demand of space heating and domestic water heating p.11
- Schedule timer operation p.11
- When setback function is enabled the setback operation will have priority over the scheduled action in the schedule timer p.12
- Operation example schedule timer based on temperature set points p.12
- Operation example schedule timer based on on off instruction p.12
- Off on on p.12
- When setback function is enabled the setback operation will have priority over the scheduled action in the schedule timer if on instruction is active if off instruction is active this will have priority over the setback function at any time the off instruction will have the highest priority p.12
- Quiet mode p.13
- Programming and consulting the schedule timer p.13
- Domestic water heating p.13
- Programming space heating p.14
- Programming quiet mode or domestic water heating p.15
- Consulting programmed actions p.15
- Tips and tricks p.16
- Operating the remote alarm option p.16
- Operating the optional remote controller p.16
- Procedure p.17
- Field settings p.17
- Field settings table p.18
- Important information regarding the refrigerant used p.20
- Disposal requirements p.20
- Aintenance p.20
- Troubleshooting p.20
- Roubleshooting p.20
- Maintenance activities p.20
- Maintenance p.20
- Isposal requirements p.20
- P403582 1 p.24
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика