Daikin RKHBRD014ADV1 [18/24] Field settings table
![Daikin RKHBRD014ADV1 [18/24] Field settings table](/views2/1797485/page18/bg12.png)
Operation manual
17
RKHBRD011~016ADV1+Y1
Indoor unit for air to water heat pump system and options
4P403582-1 – 2015.04
Field settings table
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
0 Remote control setup
00 Installation related setting 2 2~3 1 —
01 Installation related setting 0 –5~5 0.5 °C
02 Not applicable. Do not change the default value. 1 (ON) ———
03 Status: space heating schedule timer mode 1 (ON) 0/1 ——
1 Automatic storage timing for domestic water heating
00 Status: night time storage 1 (ON) 0/1 ——
01 Night time storage start time 1:00 0:00~23:00 1:00 hour
02 Status: day time storage 0 (OFF) 0/1 ——
03 Day time storage start time 15:00 0:00~23:00 1:00 hour
2 Automatic setback function
00 Status: setback operation 1 (ON) 0/1 ——
01 Setback operation start time 23:00 0:00~23:00 1:00 hour
02 Setback operation stop time 5:00 0:00~23:00 1:00 hour
3 Weather dependent set point
00 Low ambient temperature (Lo_A) –10 –20~5 1 °C
01 High ambient temperature (Hi_A) 15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti) 70 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti) 45 25~80 1 °C
4 Disinfection function
00 Status: disinfection operation 1 (ON) 0/1 ——
01 Disinfection operation day selection Fri Mon~Sun ——
02 Disinfection operation start time 23:00 0:00~23:00 1:00 hour
5 Automatic setback and disinfection set point
00 Set point: disinfection operation temperature 70 60~75 5 °C
01 Disinfection operation time duration 10 5~60 5 min
02 Leaving water setback temperature 5 0~10 1 °C
03 Room setback temperature 18 17~23 1 °C
6 Option setup
00 Installation related setting 0 (OFF) 0/1 ——
01 Installation related setting 0 (OFF) 0/1 ——
02 Installation related setting 0 (OFF) 0/1 ——
03 Installation related setting 0 (OFF) 0/1 ——
04 Installation related setting 0 0/2 1 —
7 Option setup
00 Installation related setting 1 (ON) 0/1 ——
01 Not applicable. Do not change the default value. 0 (OFF) ———
02 Installation related setting 0 (A) 0/1 ——
03 Installation related setting 0 (OFF) 0/1 ——
04 Installation related setting 0 (OFF) 0/1 ——
8 Option setup
00 Installation related setting 1 (ON) 0/1 ——
01 Installation related setting 1 (ON) 0/1 ——
02 Emergency mode 0 (OFF) 0/1 ——
03 Status: low noise level 1 1~3 1 —
04 Installation related setting 0 0~2 1 —
Содержание
- Operation manual p.1
- Indoor unit for air to water heat pump system and options p.1
- Scope of this manual p.2
- Operation manual p.2
- Introduction p.2
- General information p.2
- Domestic water heating operation p.3
- Space heating operation p.3
- Quick start up of the unit p.3
- Peration p.3
- Operation of the unit p.3
- Remote controller buttons and icons p.4
- Setting the clock p.5
- Space heating operation h p.6
- Space heating operation p.6
- Room temperature control p.6
- Leaving water temperature control p.6
- Domestic water heating operation w p.8
- Domestic water heating operation p.8
- Automatic storage p.8
- Manual storage p.9
- Defrost operation d p.10
- Defrost operation p.10
- Start up operation d p.10
- Start up operation p.10
- Reheat p.10
- Quiet mode operation s p.10
- Quiet mode operation p.10
- Other operation modes p.10
- Emergency operation p.10
- Disinfection operation p.10
- Temperature read out mode p.11
- Space heating p.11
- Simultaneous demand of space heating and domestic water heating p.11
- Schedule timer operation p.11
- When setback function is enabled the setback operation will have priority over the scheduled action in the schedule timer p.12
- Operation example schedule timer based on temperature set points p.12
- Operation example schedule timer based on on off instruction p.12
- Off on on p.12
- When setback function is enabled the setback operation will have priority over the scheduled action in the schedule timer if on instruction is active if off instruction is active this will have priority over the setback function at any time the off instruction will have the highest priority p.12
- Quiet mode p.13
- Programming and consulting the schedule timer p.13
- Domestic water heating p.13
- Programming space heating p.14
- Programming quiet mode or domestic water heating p.15
- Consulting programmed actions p.15
- Tips and tricks p.16
- Operating the remote alarm option p.16
- Operating the optional remote controller p.16
- Procedure p.17
- Field settings p.17
- Field settings table p.18
- Important information regarding the refrigerant used p.20
- Disposal requirements p.20
- Aintenance p.20
- Troubleshooting p.20
- Roubleshooting p.20
- Maintenance activities p.20
- Maintenance p.20
- Isposal requirements p.20
- P403582 1 p.24
Похожие устройства
-
Daikin EVLQ08CAV3Руководство по применению для установщика -
Daikin EVLQ08CAV3Справочное руководство для монтажника -
Daikin EVLQ08CAV3Общие правила техники безопасности -
Daikin EVLQ08CAV3Инструкция по монтажу -
Daikin EVLQ05CAV3Справочное руководство для монтажника -
Daikin EVLQ05CAV3Руководство по применению для установщика -
Daikin EVLQ05CAV3Общие правила техники безопасности -
Daikin EVLQ05CAV3Инструкция по монтажу -
Daikin EHYKOMB33AA3Справочное руководство для монтажника -
Daikin EHYKOMB33AA3Руководство по применению для установщика -
Daikin EHYKOMB33AA3Руководство по эксплуатации -
Daikin EHYKOMB33AA2Руководство по применению для установщика