14.1
Oil Management System
Oil management system fitted on unit GCU4070PXB1 is high pressure system.
The unit is fitted with a suitable sized coalescent oil separator/reservoir. The suction line has to be properly sized
to provide good oil return. Standard practice for oil traps must be followed when condensing unit or evaporator are
installed at diffeferent heights.
To assist with service/maintenance operations, shut-off valve is fitted to enable isolation.
The maximum high difference alloawance between condensing unit and evaporator should be no more than 15
meters. In case install outdoor unit under indoor unit, provide riser piping is close to indoor unit as shown below.
In case install outdoor unit above indoor unit provide oil trap as shown below (recommended 2 oil traps at 5m and
10m)
Page 20 of 177
Copyright HPL January 2021
P4115S Rev 02