Haier AV26NMVERA Инструкция по монтажу онлайн [435/531] 616694

Haier AV26NMVERA Инструкция по монтажу онлайн [435/531] 616694
435
¡ø3
if fan motor runs
no
no
no
no
if the other indoors
begin to run
yes
yes
yes
yes
yes
yes
if voltage among
B, C on wired
controller is AC
15V
if voltage between
B and C on indoor
terminal block is
15V
1. indoor PCB abnormal
2. wiring of indoor PCB
is damaged or the port
is not inserted well
no
in heating mode, fan
motor not run and
"PRE HEAT"
" DEFROST" on LCD
of wired controller will
be light.
1. in pre-heating
startup
2. in refrigerant oil
return control of
heating mode
3. in heating defrosting
4. TC2 sensor resistor
wrong
if the indoor
motor runs
wiring between
indoors and wired
controller is wrong
wiring between
indoors and wired
controller is wrong
if fan motor
rotation direction
is correct
fan capacitor abnormal
1. filter clogged
2. indoor heat exchanger
clogged
if indoor fan motor is
with AC 220V voltage
check the power source
voltage
1. indoor PCB abnormal
2. wiring of indoor PCB is damaged or the port is not
inserted well
no
remove the fan motor
wiring
indoor motor abnormal
no
no
yes
yes
if indoor motor winding
resistor is normal
if capacitor
capacity is
proper
indoor fan capacitor abnormal
wiring of indoor PCB is damaged or the port is not
inserted well

Содержание