S+S Regeltechnik AERASGARD RPS-SD [10/32] Rps sd rftm ps xx

S+S Regeltechnik AERASGARD RFTM-PS-CO2 [10/32] Rps sd rftm ps xx
10
G
AERASGARD
®
RPS - SD RFTM - PS - xx
Rev. 2022 - V12
Maintenance-free room sensor
AERASGARD
®
RPS - SD
with active output, in an elegant plastic housing with snap-on lid, base with 4-hole attach-
ment, for detecting the fine dust content (0...500 µg/m
3
). The measuring transducer converts the measurand into a standard signal of 0 -10 V (fixed).
Maintenance-free, multifunctional room sensor
AERASGARD
®
RFTM - PS
- CO2 - W
with active/switching output, automatic calibration, in an elegant
plastic housing with snap-on lid, base with 4-hole attachment, optionally with/without display, for detection of measurands air humidity (0...100 % r.H.),
temperature (0...+5C), fine dust (PM) (0...50 / 100 / 300 / 500 µg/m
3
) and CO2
content (0...2000 / 5000 ppm).
The measuring transducer converts the measurand into a standard signal of 0 -10 V or 4...20 mA (switchable). Use just one device to monitor and
control the entire indoor climate effectively. This enables energy-saving room ventilation on an as-needed basis, thereby reducing operating costs and
improving well-being. It is used in offices, hotels, convention centres, apartments, shops, etc. One sensor for every 30 m²of room area is recom
-
mended.
A long-term stable,
digital humidity and temperature sensor
guarantees exact measurement results. The CO2 content of the air is measured
using an optical
NDIR sensor
(non-dispersive infra-red technology). An optical
fine dust sensor
precisely detects
particulate (PM)
of the size
category 0.3 to 10 micrometres. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible (except for
particulate sensor).
TECHNICAL DATA
Power supply: 24 V AC ⁄ DC (± 10 %)
Power consumption:
RPS
- SD
typically < 1.5 W ⁄ 24 V DC; < 2.9 VA ⁄ 24 V AC
RFTM - PS - CO2 - W
typically < 4.4 W 24 V DC; < 6.4 VA ⁄ 24 V AC; peak current 200 mA
Output:
RPS
- SD
0 -10 V (fixed)
RFTM - PS - CO2 - W
0 -10 V
or
4...20 mA, working resistance < 800 Ω
(selectable via DIP switches,
selected version applies
uniformly
to all outputs),
with offset potentiometer (± 10 % of measuring range)
Relay output:
RPS
- SD
without changeover contact
RFTM - PS - CO2 - W
with potential-free
changeover contact
(24 V / 1 A)
(assignment selectable via DIP switches, switch point can be set)
HUMIDITY
Sensor (RH / °C):
digital humidity sensor with integrated temperature sensor,
low hysteresis, high long-term stability
Measuring range (RH): 0…100 % r. H.
Output (RH): 0 -10 V or 4...20 mA (selectable via DIP switches)
Deviation (RH): typically
± 2.0 %
(20...80 % r. H.) at +25 °C, otherwise ± 3.0 %
TEMPERATURE
Measuring range (°C): 0...+ 50 °C
Output (°C): 0 -10 V or 4...20 mA (selectable via DIP switches)
Deviation (°C): typically ± 0.2 K at +25 °C
FINE DUST
(
PM
)
Sensor (PM): optical
particulate sensor
(
PM
= particulate matter),
fine-dust sensor
with laser- and soiling-resistant technology
Measuring range (PM): multi-range switching (selectable via DIP switches)
0...50, 0...100, 0...300 or 0...500 µg/m
3
Output (PM):
RPS
- SD
0 -10 V (fixed)
RFTM - PS - CO2 - W
0 -10 V or 4...20 mA (selectable via DIP switches)
Particle size (PM):
PM
2.5
(0.3...2.5 µm);
PM
10
(0.3...10 µm)
Measuring accuracy (PM): typically ± 10 µg/m
3
10 % of measured value) at PM 2.5
typically ± 25 µg/m
3
25 % of measured value) at PM 10
Long-term stability (PM): ± 1.2 5 µg/m
3
1.25 % of measured value/year)
Service life (PM): > 10 years
CARBON DIOXIDE
(
CO2
)
Sensor (CO2): Optical
NDIR sensor
(non-dispersive infra-red technology),
with manual calibration (via zero button),
with automatic calibration (can be deactivated via DIP switches)
Measuring range (CO2): 0...2000 ppm or 0...5000 ppm (selectable via DIP switches)
Output (CO2): 0 -10 V or 4...20 mA (selectable via DIP switches)
Measuring accuracy (CO2): typically ± 30 ppm (± 3 % of measured value)
Temperature dependence
(CO2): ± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C (whichever is greater)
Pressure dependence (CO2): ± 0.13 % ⁄ mm Hg
Long-term stability (CO2): < 2 % in 15 years
Gas exchange (CO2): Diffusion Continued on next page!