S+S Regeltechnik AERASGARD RPS-SD [12/32] Rev 2022 v12

S+S Regeltechnik AERASGARD RFTM-PS-CO2 [12/32] Rev 2022 v12
12
G
AERASGARD
®
RPS - SD RFTM - PS - xx
Rev. 2022 - V12
Schematic diagram
RFTM - PS - CO2 - W
Schematic diagram
RPS - SD
4
5
6
1 2 3
SET REL.
OFFSET
ZERO
CO2 CO2 r.H.°C
121113
123 456 789
ON
DIP
ON ON
PS CO2 Mode
Sensor
CO2
Sensor
PS
NC = Normally Closed
COM = Common
NO = Normally Open
Plug for
display
–UB GND
+UB 24V AC/DC
Output CO2
[ppm]
NC
COM
NO
relay
switch
point
humidity [% r.H.]
fine dust [
µg/m
3
]
Outputs
temperature
[
°C
]
Plug for
1 2 3
123
ON
DIP
PS
Sensor
PS
–UB GND
+UB 24V AC/DC
Output PM
[µg/m³]
Plug for
DIP switch
RFTM - PS
- xx
Fine dust
(
PM
) Measuring range
DIP 1 DIP 2
0...50 µg/m
3
OFF OFF
0...100 µg/m
3
(default)
O N
OFF
0...300 µg/m
3
OFF
O N
0...500 µg/m
3
O N O N
Fine dust
(
PM
) Particle size
DIP 3
PM 2.5 (default)
O N
PM 10 OFF
CO2
content DIP 4
0...2000 ppm (default) OFF
0...5000 ppm
O N
CO2 autom. calibration
DIP 6
deactivated OFF
activated (default)
O N
Relay assignment DIP 7 DIP 8
CO2 (default) 600...1900 ppm / 900...4700 ppm OFF OFF
Fine dust 10 %...95 % of measuring range
O N
OFF
Temperature +5...+48 °C OFF
O N
Humidity 10...95 % r.H.
O N O N
Output DIP 9
Voltage 0 -10 V (default) OFF
Current 4...20 mA
O N
Note:
DIP 5
is not assigned !
DIP switch
RPS - SD
Fine dust
(
PM
) Measuring range
DIP 1 DIP 2
0...50 µg/m
3
OFF OFF
0...100 µg/m
3
(default)
O N
OFF
0...300 µg/m
3
OFF
O N
0...500 µg/m
3
O N O N
Fine dust
(
PM
)
Particle size DIP 3
PM 2.5 (default)
O N
PM 10 OFF

Содержание