ioLogik W5300 Planning and Assistance
5-6
Step 9: After adding Active OPC Server you should see the following screen. Click the Refresh button to use
ioAdmin to monitor and configure the ioLogik W5300.
Expanding Input/Output Channels
Scenario: A monitoring system for a pumping station does not have enough I/O channels, and the user would
like to add more I/O channels to meet system requirements. In addition to the existing 4 AIs, 8 DIOs, and 2
Relay Outputs, they are using the ioLogik E1210 and E1211 to add an additional 16 DIs and 16 DOs.
Implementation:
Step 1: Connect to the ioLogik E1210 and E1211 and start the Web Consoles for these two products.
Step 2: Configure and export the configuration files of these two models. The file names will be ik1210.txt and
ik1211.txt.
Step 3: Use Ethernet cables to daisy-chain the W5340, E1210, and E1211, and connect to the host PC through
the E1211’s Ethernet port.
Step 4: Start ioAdmin with the selected W5340 and choose I/O Expansion.
ioLogik W5340
Active OPC Server