Grundfos MAGNA3 25-40 N 180 97924336 [6/1656] Scope of delivery

Grundfos MAGNA3 D 32-80 180 97924451 [6/1656] Scope of delivery
English (GB)
6
1.2 Safety symbols on the pump
2. Receiving the product
2.1 Inspecting the product
Check that the product received is in accordance with the order.
Check that the voltage and frequency of the product match the
voltage and frequency of the installation site. See section
6.3.1 Nameplate.
2.2 Scope of delivery
2.2.1 Plug-connected single-head pump
Fig. 1 Plug-connected single-head pump
The box contains the following items:
MAGNA3 pump
insulating shells
•gaskets
quick guide
safety instructions
one ALPHA plug.
2.2.2 Plug-connected twin-head pump
Fig. 2 Plug-connected twin-head pump
The box contains the following items:
MAGNA3 pump
•gaskets
•quick guide
safety instructions
two ALPHA plugs.
2.2.3 Terminal-connected single-head pump
Fig. 3 Terminal-connected single-head pump
The box contains the following items:
MAGNA3 pump
insulating shells
•gaskets
•quick guide
safety instructions
box with terminal and cable glands.
2.2.4 Terminal-connected twin-head pump
Fig. 4 Terminal-connected twin-head pump
The box contains the following items:
MAGNA3 pump
•gaskets
•quick guide
safety instructions
two boxes with terminals and cable glands.
Check the position of the clamp before you tighten
the clamp. Incorrect position of the clamp will cause
leakage from the pump and damage the hydraulic
parts in the pump head.
Fit and tighten the screw that holds the clamp to 8
Nm ± 1 Nm.
Do not apply more torque than specified even though
water is dripping from the clamp. The condensed
water is most likely coming from the drain hole under
the clamp.
Pumps tested with water containing anticorrosive
additives are taped on the inlet and outlet ports to
prevent residual test water from leaking into the
packaging. Remove the tape before installing the
pump.
TM06 7224 3216
8Nm!
TM06 7225 3216TM05 8159 2013TM06 6791 2316

Содержание

Похожие устройства

Скачать