Cuenod C 24 GX 507 T1 [5/48] Assembly

Cuenod C 30 GX 507 T1 [5/48] Assembly
02/2008 - Art. Nr. 13 019 866A 5
Installation
Assembly
Burner
The burner is secured on the boiler with
the flange supplied. The drilling
recommended for Ø b is written in
boldfaced figures on the drawing. If Ø a
on the boiler exceeds the maximum Ø
on the drawing (see technical data),
provision should be made for a cover
plate in front.
• Mount the flange and its gasket on the
boiler.
• Check the tightness.
The burner is mounted with the volute
casing upwards but it can be mounted
with the volute casing downwards. In
such a case :
• remove screws V,
• make TF rotate by 180°,
• replace and tighten screw V.
The adhesive front plate is suplied in the
document folder. It must be sticked on
the cover at a temperature above 10°C.
• Insert the blast tube into the flange.
• Hook the burner using the bayonet
system.
• Tighten the three nuts.
When the generator incorporates a door
for access to the furnace, pack the
space 1 between the quarl and the
blast tube with a refractory material (not
supplied).
Gas manifold
• Check presence and position of O-ring
in manifold flange.
• When fitting gas manifold, valve coils
must be in the vertical top position.

Содержание