Table 7. Power-Up Options
Button Description
A
bswitch position turns on all LCD
segments.
O switch position displays the software
version number.
f switch position displays the model
number.
L
Starts the Calibration mode. The Tester
displays CAL and enters Calibration mode
when the button is released.
Note
Power Up options are active when the button is
pressed.
Making Measurements
The figures on the following pages show how to make
measurements.
When connecting the test leads to the circuit or device,
connect the common (COM) test lead before connecting
the live lead; when removing the test leads, remove the
live lead before removing the common test lead.
XWWarning
To avoid electric shock, injury, or damage to
the Tester, disconnect circuit power and
discharge all high-voltage capacitors before
testing.
Содержание
- 1503 insulation testers users manual 1
- Insulation testers 1
- Users manual 1
- Limited warranty and limitation of liabilit 2
- Limited warranty and limitation of liability 2
- To register your product online visit register fluke com 2
- Table of contents 3
- Title page 3
- List of tables 5
- Table title page 5
- Figure title page 7
- List of figures 7
- Contacting fluke 9
- Insulation testers 9
- Introduction 9
- Safety information 10
- Xw warning 10
- Battery saver sleep mode 12
- Rotary switch positions 12
- Unsafe voltage 12
- Buttons and indicators 13
- Understanding the display 15
- Xw warning 15
- Cal err 16
- Input terminals 17
- Power up options 17
- Making measurements 18
- Xw warning 18
- Measuring earth bond resistance 19
- Measuring volts 19
- Measuring insulation resistance 21
- Measuring polarization index and dielectric absorption ratios model 1507 22
- Using the compare function model 1507 24
- Cleaning 25
- Testing the batteries 25
- Testing the fuse 26
- Xw warning 26
- Replacing the batteries and fuse 27
- Xw warning 27
- 1503 users manual 28
- General specifications 28
- Specifications 28
- Ac dc voltage measurement 29
- Accuracy 29
- Insulation testers specifications 29
- Of rdg digits 29
- Range resolution 50 hz to 400 hz 29
- V 0 v 2 3 29
- Earth bond resistance measurement 30
- Insulation specifications 30
- Model 1507 31
- En61557 specification 32
- Model 1503 32
- Insulation resistance maximum and minimum display values 34
- Insulation resistance maximum and minimum display values cont 35
- Insulation resistance maximum and minimum display values cont 36
- Insulation resistance maximum and minimum display values cont 37
- Earth bond resistance maximum display values 38
Похожие устройства
- Panasonic NN-C2000P Инструкция по эксплуатации
- Crate V1512 Инструкция по эксплуатации
- Beko CN 332220 S Инструкция по эксплуатации
- Hotpoint-Ariston LSF 7237 Инструкция по эксплуатации
- Supra TBS-A2160 Инструкция по эксплуатации
- Leica DISTO D3a 300015 Инструкция по эксплуатации
- Panasonic NN-B756 Инструкция по эксплуатации
- Fluke 1503 Инструкция по эксплуатации
- Crate V3112T Инструкция по эксплуатации
- Beko CSK 38000 X Инструкция по эксплуатации
- Beko DFS 1500 Инструкция по эксплуатации
- Supra SSM-W12 Инструкция по эксплуатации
- Ada Metrix 60 А00105 Инструкция по эксплуатации
- Fluke 1523 Инструкция по эксплуатации
- X-Line SNIPER 60 М X00119 Инструкция по эксплуатации
- Beko CS 338020 X Инструкция по эксплуатации
- Crown CTS2000 Инструкция по эксплуатации
- LG LD-4324MH Инструкция по эксплуатации
- Supra SSM-T26 Инструкция по эксплуатации
- Fluke 1524 Инструкция по эксплуатации
Скачать
Случайные обсуждения