ABB ACH550-01-04A1-4+B055 [19/32] Technical data

ABB ACH550-01-04A1-4+B055 [19/32] Technical data
ACH550 BACnet User’s Manual 19
Technical Data
Technical Data
Protocol Implementation Conformance Statement (PICS)
PICS Summary
BACnet Standard Device Profile
This version of ACH550 BACnet fully conforms to the 'Application-Specific
Controller' standard device profile (B-ASC).
Services Supported
The following services are supported by the ACH550:
I-Am (Response to Who-Is, also broadcast on power-up & other reset)
I-Have (Response to Who-Has)
ReadProperty
WriteProperty
DeviceCommunicationControl
ReinitializeDevice
Data Link Layer
The ACH550 implements MS/TP (Master) Data Link Layer. All standard MS/TP baud
rates are supported (9600, 19200, 38400 & 76800).
MAC ID / Device Object Instance
The ACH550 supports separate MAC ID and Device Object Instance parameters:
Set the MAC ID using drive parameter 5302. Default: 5302 = 1.
Set the Device Object Instance using drive parameters 5311 and 5317. Default:
Both 5311 and 5317 = 0, which causes the MAC ID to “double” ast he Device
Object Instance. For Device Object Instance values not linked to the MAC ID, set
ID values using 5311 and 5317 = 0.
For IDs in the range of 1 to 65,535: Parameter 5311 sets the ID directly (5317
must be 0). For example, the following values set the ID to 49134: 5311 =
49134 and 5317 = 0.
For IDs > 65,535: The ID equals 5311’s value plus 10,000 times 5317’s value.
For example, the following values set the ID to 71,234: 5311 = 1234 and 5317
= 7.

Содержание

Похожие устройства

Скачать