Yaskawa CIMR-UU4A0240A [257/644] H terminal functions

Yaskawa CIMR-UU2A0054F [257/644] H terminal functions
Setting Function Page
8 During Baseblock (N.O.) 260
9 Frequency Reference Source 260
A Run Command Source 260
B Torque Detection 1 (N.O.) 261
C Frequency Reference Loss 261
E Fault 261
F Through Mode 261
10 Minor Fault 261
11 Fault Reset Command Active 261
12 Timer Output 261
13 Speed Agree 2 261
14 User-Set Speed Agree 2 262
15 Frequency Detection 3 262
16 Frequency Detection 4 263
17 Torque Detection 1 (N.C.)
261
18 Torque Detection 2 (N.O.)
19 Torque Detection 2 (N.C.) 261
1A During Reverse 263
1B During Baseblock (N.C.) 264
1C Motor 2 Selection 264
1D During regeneration 264
1E Restart Enabled 264
1F Motor Overload Alarm (oL1) 264
20 Drive Overheat Pre-Alarm (oH) 264
22 Mechanical Weakening Detection 264
2F Maintenance Period 264
Setting Function Page
30 During Torque Limit 264
31 During Speed Limit 265
32 During Speed Limit in Torque Control 265
33 Zero Servo Complete 265
37 During Frequency Output 265
38 Drive Enabled 265
39 Power Consumption Pulse Output 265
3A Regenerated Power Pulse Output 265
3C LOCAL/REMOTE Status 265
3D During Speed Search 266
3E PID Feedback Low 266
3F PID Feedback High 266
4C During Fast Stop 266
4D oH Pre-Alarm Time Limit 266
60 Internal Cooling Fan Alarm 266
61 Rotor Position Detection Completed 266
62
MEMOBUS Register 1 (Selected with H2-07 and
H2-08)
266
63
MEMOBUS Register 2 (Selected with H2-09 and
H2-10)
266
64 During Commercial Power Operation 266
90 DriveWorksEZ Digital Output 1
26691 DriveWorksEZ Digital Output 2
92 DriveWorksEZ Digital Output 3
100 to 192 Functions 0 to 92 with Inverse Output 266
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status Description
Open Drive is stopped.
Closed A Run command is input or the drive is in deceleration or DC injection.
ON
ON
OFF
OFF
ONOFF
Run command
Baseblock
command
Output
frequency
During Run
Figure 5.66 During Run Time Chart
Setting 1: Zero Speed
Terminal closes when
the output frequency or motor speed (CLV, CLV/PM) becomes less than or equal to the minimum output
frequency set to E1-09 or b2-01.
5.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual
257
5
Parameter Details