Yaskawa CIMR-UU4A0240A [85/644] Main circuit terminal and motor wiring

Yaskawa CIMR-UU4A0034F [85/644] Main circuit terminal and motor wiring
Drive
Model
Terminal
For USA and Canada For South America
Screw
Size
Tightening
Torque
N·m (lb.in.)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
4o0180
R/L1, S/L2, T/L3
35 × 2
(2 × 2P)
25 to 95 × 2
(3 to 4/0 × 2P)
25 × 2P
(3 × 2P)
25 to 95 × 2P
(3 to 4/0 × 2P)
M10
15 to 20
(133 to 177)
U/T1, V/T2, W/T3
35 × 2
(2 × 2P)
25 to 95 × 2
(3 to 4/0 × 2P)
25 × 2P
(3 × 2P)
25 to 95 × 2P
(3 to 4/0
× 2P)
M10
25
(3)
25 to 70
(4 to 2/0)
25
(3)
25 to 70
(3 to 2/0)
M10
17.7 to 22.6
(156 to 200)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
4o0216
R/L1, S/L2, T/L3
50 × 2
(1/0 × 2P)
35 to 95 × 2
(2 to 4/0 × 2P)
35 × 2P
(1 × 2P)
25 to 95 × 2P
(3 to 4/0 × 2P)
M10
15 to 20
(133 to 177)
U/T1, V/T2, W/T3
50 × 2
(1/0 × 2P)
35 to 95 × 2
(2 to 4/0 × 2P)
35 × 2P
(1 × 2P)
25 to 95 × 2P
(3 to 4/0
× 2P)
M10
25
(3)
25 to 95
(4 to 4/0)
35
(1)
25 to 95
(3 to 4/0)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
4o0240
R/L1, S/L2, T/L3
50 × 2
(1/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
50 × 2P
(1/0 × 2P)
35 to 95 × 2P
(1 to 4/0 × 2P)
M10
15 to 20
(133 to 177)
U/T1, V/T2, W/T3
50 × 2
(1/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
50 × 2P
(1/0 × 2P)
35 to 95 × 2P
(1 to 4/0
× 2P)
M10
35
(2)
35 to 95
(2 to 4/0)
50
(1/0)
35 to 95
(1 to 4/0)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
4o0302
<1>
R/L1, S/L2, T/L3
70 × 2
(3/0 × 2P)
50 to 95 × 2
(1/0 to 4/0 × 2P)
70 × 2P
(3/0 × 2P)
50 to 95 × 2P
(1/0 to 4/0 × 2P)
M10
15 to 20
(133 to 177)
U/T1, V/T2, W/T3
70 × 2
(3/0 × 2P)
50 to 95 × 2
(1/0 to 4/0
× 2P)
70 × 2P
(3/0 × 2P)
50 to 95 × 2P
(1/0 to 4/0 × 2P)
M10
35
(1)
35 to 150
(1 to 300)
70
(3/0)
35 to 150
(1 to 300)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
4o0361
<1>
R/L1, S/L2, T/L3
95 × 2
(4/0 × 2P)
70 to 95 × 2
(3/0 to 4/0 × 2P)
95 × 2P
(4/0 × 2P)
70 to 95 × 2P
(3/0 to 4/0 × 2P)
M10
15 to 20
(133 to 177)
U/T1, V/T2, W/T3
95 × 2
(4/0 × 2P)
70 to 95 × 2
(3/0 to 4/0
× 2P)
95 × 2P
(4/0 × 2P)
70 to 95 × 2P
(3/0 to 4/0 × 2P)
M10
50
(1/0)
50 to 150
(1/0 to 300)
95
(4/0)
70 to 150
(3/0 to 300)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
4o0414
<1>
R/L1, S/L2, T/L3
150 × 2
(300 × 2P)
95 to 150 × 2
(4/0 to 300 × 2P)
95 × 2P
(4/0 × 2P)
95 to 150 × 2P
(4/0 to 300 × 2P)
M12
25 to 35
(221 to 310)
U/T1, V/T2, W/T3
150 × 2
(300 × 2P)
95 to 150 × 2
(4/0 to 300
× 2P )
95 × 2P
(4/0 × 2P)
95 to 150 × 2P
(4/0 to 300 × 2P )
M12
50
(1/0)
50 to 240
(1/0 to 400)
95
(4/0)
70 to 240
(3/0 to 400)
M12
31.4 to 39.2
(278 to 347)
p1, n1
2.5
(14)
2.5 to 4
(14 to 12)
2.5
(14)
2.5 to 4
(14 to 12)
M4
1.2 to 2.0
(10.6 to 17.7)
<1> Take additional measures in accordance with IEC/EN 61800-5-1 when wiring an EMC filter is installed. Refer to the Technical Manual for details.
u
Main Circuit Terminal and Motor Wiring
This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.
NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should
match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.
3.8 Main Circuit Wiring
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual
85