Yaskawa CIMR-UU4A0240A [314/644] O2 02 stop key function selection

Yaskawa CIMR-UU2A0042F [314/644] O2 02 stop key function selection
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already applied when switching from
LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious injury. Check all mechanical or electrical connections
thoroughly before making any setting changes to o2-01 and b1-07. Table 5.43 lists the setting combinations for o2-01 and b1-07.
Table 5.43 LO/RE Key and b1-07
o2-01 b1-07 Switch from LOCAL to REMOTE Switch from REMOTE to LOCAL
0
0 Not possible Not possible
1 Not possible Not possible
1
0
Will not run until a new Run command is
entered.
Run not possible
1
If a Run command is entered, the drive will start
running as soon as the LO/RE key is pushed to
change from LOCAL to REMOTE.
Run not possible
n
o2-02: STOP Key Function Selection
Determines
if the
STOP key on the digital operator will stop drive operation when the drive is controlled from a remote source
(i.e., not from digital operator).
No. Name Setting Range Default
o2-02 STOP Key Function Selection 0, 1 1
Setting 0: Disabled
Setting 1: Enabled
The STOP key will terminate drive operation even if the Run command source is not assigned to the digital operator. Cycle
the Run command to restart the drive if the drive has been stopped by pressing the STOP key.
n
o2-03: User Parameter Default Value
After
completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the values,
parameter A1-03 (Initialize Parameters) will offer the choice of "1110: User Initialize". Selecting 1110 resets all parameters
to the user-set default values. Refer to A1-03: Initialize Parameters on page 153 for details on drive initialization.
No. Name Setting Range Default
o2-03 User Parameter Default Value 0 to 2 0
Setting 0: No Change (Awaiting Command)
Setting 1: Set User Initialize Values
The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing the
ENTER key saves the values and returns the display to 0.
Setting 2: Clear User Initialize Values
All user-set defaults for “User Initialize” are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values and
returns the display to 0.
n
o2-04: Drive Model Selection
Set
this parameter when replacing the control board or the terminal board. Refer to Defaults by Drive Model and Duty Rating
ND/HD on page 536 for information on drive model selection.
NOTICE: Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.
No. Name Setting Range Default
o2-04 Drive Model Selection -
Determined by
drive capacity
Note: Change o2-04 setting only when necessary.
n
o2-05: Frequency Reference Setting Method Selection
Determines if the ENTER key must be pressed after changing the frequency reference using the digital operator while in the
Drive Mode.