Yaskawa CIMR-UU4A0240A [460/644] C7 voltage adjustment

Yaskawa CIMR-UU4A0021F [460/644] C7 voltage adjustment
No.
(Addr.
Hex)
Name LCD Display Description Values Page
C6-03
(0225)
Carrier Frequency Upper
Limit
CarrierFreq Max
All Modes
Note: C6-04 and C6-05 are available only in V/f and
V/f w/PG control modes.
Determines the upper and lower limits for the carrier frequency.
In OLV, C6-03 determines the upper limit of the carrier
frequency.
Carrier Frequency
E1-04
Max Output
Frequency
Output Frequency
× (C6-05)
Output
Frequency
C6-03
C6-04
Default:
<2>
Min.: 4.0 kHz
Max.: 10.0 kHz
203
C6-04
(0226)
Carrier Frequency
Lower Limit
CarrierFreq Min
Default:
<2>
Min.: 4.0 kHz
Max.: 10.0 kHz
203
C6-05
(0227)
Carrier Frequency
Proportional Gain
CarrierFreq Gain
Default:
<2>
Min.: 0
Max.: 99
203
C6-09
(022B)
Carrier Frequency
during Rotational Auto-
Tuning
Carrier in tune
0: Fc = 5kHz
1: Fc = C6-03
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM AOLV/PM
OLV
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM AOLV/PM
OLV
CLV/PM
CLV
0: Carrier Frequency = 4 kHz. In PM control modes, this value
is 2 kHz.
1: Setting value for C6-03. In PM control modes, this value is
the carrier frequency set in C6-02.
Default: 0
Range: 0, 1
204
<1> Default setting value
is determined by parameters A1-02, Control Method Selection, C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
<2> Default setting value is determined by parameter C6-02, Carrier Frequency Selection.
u
C7: Voltage Adjustment
No.
(Addr.
Hex)
Name LCD Display Description Values Page
C7-43
(112A)
Input Voltage Offset
Adjustment
InputVolt Offset
All Modes
Adjusts the offset for the input voltage circuit when the control
board is replaced.
0000: Standard
0002: Offset adjustment not required
Default: 0000
Range: 0000 to
9999
204
C7-56
(1107)
Power Factor Control
Selection
PF Control Sel
0: PF Ctrl Disabled
1: PF Ctrl Enabled
All Modes
0: Power factor control disabled
1: Power factor control enabled
Default: 0
Range: 0, 1
204
C7-60
(0B1C)
Output Voltage Limit
Mode Selection
V Out Limit Sel
0: Limit Harmonics
1: Improve PF
All Modes
0: Harmonic suppression priority mode
1: High output voltage mode
Default: 1
Range: 0, 1
204