Yaskawa CIMR-UU4A0240A [516/644] T2 pm motor auto tuning

Yaskawa CIMR-UU4A0021A [516/644] T2 pm motor auto tuning
No.
(Addr.
Hex)
Name LCD Display Description Values Page
T1-09
(0709)
Motor No-Load Current
(Stationary Auto-
Tuning)
No-Load Current
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVOLV CLV
Sets the no-load current for the motor. After setting the motor
capacity to T1-02 and the motor rated current to T1-04, this
parameter will automatically display the no-load current for a
standard 4-pole Yaskawa motor. Enter the no-load current as
indicated on the motor test report.
Default: –
Min.: 0 A
Max.: T1-04
139
T1-10
(070A)
Motor Rated Slip
(Stationary Auto-
Tuning)
Motor Rated Slip
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVOLV CLV
Sets the motor rated slip. After setting the motor capacity to
T1-02, this parameter will automatically display the motor slip
for a standard 4-pole Yaskawa motor. Enter the motor slip as
indicated on the motor test report.
Default: –
Min.: 0.00 Hz
Max.: 20.00 Hz
139
T1-11
(070B)
Motor Iron Loss Mtr Iron Loss(W)
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f V/f w PG
Sets the iron loss for determining the Energy Saving coefficient.
The value is set to E2-10 (motor iron loss) set when the power is
cycled. If T1-02 is changed, a default value appropriate for the
motor capacity that was entered will appear.
Default: 14 W
<5>
Min.: 0
Max.: 65535
139
<1> The availability of certain Auto-Tuning methods is determined by the control mode selected for the drive.
<2> Default setting is determined by parameter A1-02, Control Method Setting.
<3> Default setting is determined by parameter o2-04, Drive Model Selection.
<4>
Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<5> Default setting value differs depending on the motor code value and motor parameter settings.
u
T2: PM Motor Auto-Tuning
No.
(Addr.
Hex)
Name LCD Display Description Values Page
T2-01
(0750)
<1>
PM Motor Auto-Tuning
Mode Selection
PM Tuning Mode
0: Standard Tuning
1: Tune-No Rotate
2: Term Resistance
3: Z-Pulse Tuning
8: Inertia Tuning
9: Tune ASR gain
11: IndVoltConstTun
13: High Freq Tun
14: PM rotation tune
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM AOLV/PM CLV/PMOLV/PM AOLV/PM CLV/PM
0: PM Motor Parameter Settings
1: PM Stationary Auto-Tuning
2: PM Stationary Auto-Tuning for Stator Resistance
3: Z Pulse Offset Tuning
8: Inertia Tuning
9: ASR Gain Auto-Tuning
11: Back EMF Constant Tuning
13: High Frequency Injection Parameter Tuning
14: PM Rotational Auto-Tuning
Note: 1. Settings 8 and 9 may not be available when
gears are between the machine and the motor
shaft.
2. For special-purpose motors, Yaskawa
recommends Back EMF Constant Tuning after
performing Stationary Auto-Tuning. Back
EMF Constant Tuning rotates the motor to
measure the actual induction voltage constants,
and allows for more accurate control than
Stationary Auto-Tuning alone.
Default: 0
Range: 0 to 3;
8, 9, 11, 13, 14
<2>
139
T2-02
(0751)
PM Motor Code
Selection
PM Mtr Code Sel
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM AOLV/PM CLV/PMOLV/PM AOLV/PM CLV/PM
Enter the motor code when using a Yaskawa PM motor. After
entering the motor code, the drive automatically sets parameters
T2-03 through T2-09. Set parameters T2-10 to T2-14 according
the motor nameplate or the motor test report. When using a motor
without a supported motor code or a non-Yaskawa motor, set
FFFF and adjust the other T2 parameters according to the motor
nameplate or the motor test report.
Default:
<3>
Min: 0000
Max: FFFF
140
B.14 T: Motor Tuning
516
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual