Yaskawa CIMR-UU4A0240A [95/644] Sinking sourcing mode selection for safe disable inputs

Yaskawa CIMR-UU2A0042A [95/644] Sinking sourcing mode selection for safe disable inputs
u
Sinking/Sourcing Mode Selection for Safe Disable Inputs
Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the Safe Disable
inputs H1 and H2 as shown in Table 3.11 (Default: Source mode, internal power supply). Refer to Switches and Jumpers
on the Terminal Board on page 92 for locating jumper S3.
Table 3.12 Safe Disable Input Sink/Source/External Power Supply Selection
Mode Drive Internal Power Supply External 24 Vdc Power Supply
Sinking Mode
24 Vdc
H1
H2
HC
Jumper S3
24 Vdc
H1
H2
HC
External
24 Vdc
Jumper S3
Sourcing Mode
24 Vdc
H1
H2
HC
Jumper S3
24 Vdc
H1
H2
HC
External
24 Vdc
Jumper S3
u
Using the Pulse Train Output
The pulse train output terminal MP can supply power or be used with an external power supply.
NOTICE: Connect
peripheral devices
in accordance with the specifications. Failure to comply may cause unexpected drive operation, and
can damage the drive or connected circuits.
n
Using Power from the Pulse Output Terminal (Source Mode)
The high voltage level of the pulse output terminal depends on the load impedance.
Load Impedance R
L
(kΩ) Output Voltage V
MP
(V) (insulated)
1.5 kΩ 5 V
4 kΩ 8 V
10 kΩ 10 V
Note:
The load resistance needed in order to get a certain high level voltage V
MP
can be calculated by: R
L
= V
MP
2 / (12 – V
MP
)
MP
AC
V
MP
R
L
Load Impedance
Figure 3.33 Pulse Output Connection Using Internal Voltage Supply