TECHNICAL SPECIFICATION
EWAT~B-XS/L
MODEL
EWAT600B
-XSA2
EWAT660B
-XSA2
EWAT700B
-XSA2
COOLING
PERFORMANCE
Capacity - Cooling
kW
607
660
701
Capacity control - Type
Step
Step
Step
Capacity control - Minimum
capacity
%
11.9
11.1
16.7
Unit power input - Cooling
kW
198
214
231
EER
3.05
3.08
3.03
ESEER
4.08
4.12
4.05
ESEER (+opt FANMOD
(5)
)
4.25
4.33
4.27
IPLV
4.78
4.82
4.75
IPLV (+opt FANMOD
(5)
)
5.03
5.10
5.08
SEER
(1)
4.42
4.47
4.46
SEER (+opt FANMOD
(5)
)
(1)
4.68
4.72
4.74
DIMENSIONS
Height
mm
2540
2540
2540
Width
mm
2236
2236
2236
Length
mm
5874
6774
6774
WEIGHT
Unit Weight
(SL Version)
kg
3708 (3873)
4083 (4248)
4231 (4396)
Operating Weight
(SL Version)
kg
3751 (3916)
4125 (4290)
4267 (4432)
WATER HEAT
EXCHANGER
Type
(2)
PHE
PHE
PHE
Water Volume
l
42
50
50
Water flow rate
l/s
29.1
31.6
33.6
Water pressure drop
(4)
kPa
74.6
70.2
78.5
Insulation material
Closed cell
Closed cell
Closed cell
AIR HEAT EXCHANGER
Type
(2)
MCH
MCH
MCH
FAN
Type
(2)
DPT
DPT
DPT
Drive
(2)
On-off
On-off
On-off
Diameter
mm
800
800
800
Nominal air flow
l/s
60918
65994
71071
Quantity
No.
12
13
14
Speed
rpm
900
900
900
Motor input
kW
21.5
23.3
25.1
COMPRESSOR
Type
Scroll
Scroll
Scroll
Oil charge
l
34.0
35.9
37.8
Quantity
No.
6
6
6
SOUND LEVEL
(3)
Sound Power - Cooling
(SL Version)
dB(A)
99 (96)
99.0 (96)
99 (96)
Sound Pressure level@1m
distance Cooling
(SL Version)
dB(A)
77.8 (74.8)
77.9 (74.8)
78.3 (75.2)
REFRIGERANT CIRCUIT
Refrigerant type
R32
R32
R32
Refrigerant charge
kg
80
92
100
N. of circuits
No.
2
2
2
PIPING CONNECTIONS
Evaporator water
inlet/outlet
mm
114.3
114.3
114.3
All the performances (Cooling capacity, unit power input in cooling and EER) are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C,
unit at full load operation; operating fluid: Water; fouling factor = 0.
(1) In accordance with standard EN14825:2013, comfort low temperature, average climate. SEER and µs values applicable Ecodesign regulation: (EU) No
2016/2281.
(2) PHE: Plate Heat Exchanger; S&T: Single Pass Shell & Tube; MCH: Microchannel; DPT: Direct Propeller Type; DOL: Direct On Line - VFD: Inverter
(3) Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and Eurovent 8/1 for
Eurovent certified units. The certification refers only to the overall sound power level, the sound pressure is calculated from the sound power level and are
for information only and not considered binding. The minimum capacity indicated is referred to unit operating at standard Eurovent conditions. Dimensions
and weights are for indication only and not considered binding. Before designing the installation, consult the official drawings available from the factory at
request. All the data are referred to standard unit without options. All data are subject to change without notice.
(4) The value refers to the pressure drops in the evaporator only.
(5) Option FANMOD consist in Continuous Fan Speed Regulation and improves part load operation. Single-V units are standardly equipped with continuous
fan control. Multi-V units require opt 99