Daikin EWAT290B-SRA1 [42/62] Ewat b xl

Daikin EWAT260B-SRB2 [42/62] Ewat b xl
SOUND LEVELS
42/62
EWAT~B-XL
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Sound
Power
MODEL
63 Hz
125 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
db (A)
85
61.5
66.4
62.5
60.2
57.6
51.9
67.5
85
115
63.1
68.0
64.0
61.8
59.2
53.5
69.1
87
145
64.1
69.0
65.0
62.8
60.2
54.4
70.1
89
180
65.6
70.5
66.5
64.3
61.7
56.0
71.6
91
185
64.9
69.8
65.9
63.6
61.0
55.3
70.9
89
200
65.7
70.5
66.6
64.4
61.8
56.0
71.7
91
220
65.7
70.6
66.7
64.4
61.8
56.1
71.7
91
230
66.3
71.2
67.2
65.0
62.4
56.7
72.3
92
250
66.2
71.1
67.1
64.9
62.3
56.5
72.2
92
280
67.0
71.9
67.9
65.7
63.1
57.3
73.0
93
300
66.3
71.2
67.2
65.0
62.4
56.7
73.1
93
310
67.0
71.9
68.0
65.7
63.1
57.4
73.0
93
320
67.0
71.9
68.0
65.8
63.2
57.4
73.1
93
360
67.3
72.2
68.3
66.0
63.4
57.7
73.3
93
370
67.3
72.2
68.2
66.0
63.4
57.6
73.3
93
430
67.9
72.8
68.8
66.6
64.0
58.2
73.9
94
470
68.0
72.9
68.9
66.7
64.1
58.3
74.0
94
540
68.4
73.3
69.4
67.1
64.5
58.8
74.4
95
600
68.8
73.7
69.8
67.5
64.9
59.2
74.8
96
660
68.8
73.7
69.8
67.5
64.9
59.2
74.8
96
700
69.2
74.0
70.1
67.9
65.3
59.5
75.2
96
EWAT~B-XR
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Sound
Power
MODEL
63 Hz
125 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
db (A)
85
54.2
59.1
55.1
52.9
50.3
44.6
60.2
78
115
57.9
62.8
58.8
56.6
54.0
48.3
63.9
82
145
59.6
64.5
60.5
58.3
55.7
50.0
65.6
84
180
59.3
64.1
60.2
58.0
55.4
49.6
65.3
84
185
61.6
66.5
62.6
60.4
57.7
52.0
67.7
86
200
59.5
64.4
60.5
58.2
55.6
49.9
65.5
85
220
59.8
64.7
60.7
58.5
55.9
50.1
65.8
85
230
60.7
65.6
61.6
59.4
56.8
51.1
66.7
86
250
60.3
65.2
61.2
59.0
56.4
50.6
66.3
86
280
61.1
66.0
62.0
59.8
57.2
51.4
67.1
87
300
61.5
66.4
62.4
60.2
57.6
51.8
67.5
87
310
61.2
66.1
62.2
59.9
57.3
51.6
67.2
87
320
61.4
66.3
62.3
60.1
57.5
51.8
67.4
87
360
61.7
66.6
62.7
60.5
57.9
52.1
67.8
88
370
61.7
66.6
62.6
60.4
57.8
52.0
67.7
88
430
62.3
67.2
63.3
61.0
58.4
52.7
68.3
88
470
62.5
67.3
63.4
61.2
58.6
52.8
68.5
89
540
62.9
67.8
63.9
61.6
59.0
53.3
68.9
89
600
63.2
68.1
64.2
61.9
59.3
53.6
69.2
90
660
63.3
68.1
64.2
62.0
59.4
53.6
69.3
90
700
63.6
68.5
64.6
62.3
59.7
54.0
69.6
91
Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level.
The sound data in the Octave band spectrum is for intended for reference only and not considering binding.
The sound pressure is calculated from the sound power level and are for information only and not considered binding.

Содержание