Daikin EWAT290B-SRA1 [39/62] Electrical specifications

Daikin EWAT260B-SRB2 [39/62] Electrical specifications
ELECTRICAL SPECIFICATIONS
39/62
EWAT~B-XR
MODEL
EWAT320B-
XRA2
EWAT360B-
XRA1
EWAT430B-
XRA2
EWAT470B-
XRA2
EWAT540B-
XRA2
POWER SUPPLY
Phases
No.
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
570
565
575
638
643
717
Nominal running current
cooling
A
194
204
221
250
276
319
Maximum running current
A
253
250
259
325
332
408
Maximum current for wires
sizing
A
278
275
285
358
365
449
FANS
Nominal running current
cooling
A
12
14
14
16
19
21
COMPRESSORS
Phases
No.
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
Maximum running current
A
240
235
245
309
314
387
Starting method
DOL
DOL
DOL
DOL
DOL
DOL
MODEL
EWAT600B-
XRA2
EWAT660B-
XRA2
POWER SUPPLY
Phases
No.
3
3
3
Frequency
Hz
50
50
50
Voltage
V
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
UNIT
Maximum inrush current
A
791
795
800
Nominal running current
cooling
A
352
381
410
Maximum running current
A
486
492
499
Maximum current for wires
sizing
A
534
542
549
FANS
Nominal running current
cooling
A
25
27
29
COMPRESSORS
Phases
No.
3
3
3
Voltage
V
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
Maximum running current
A
461
466
470
Starting method
DOL
DOL
DOL
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
The data are referred to the standard unit without options.
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice. Please refer to unit nameplate data.