OPTIONS (TECHNICAL DATA)
45/62
Water heat exchanger - maximum/maximum water Δt
The minimum and maximum allowed Δt at full load conditioins are respectively 3 °C and 8°C. Contact factory
in case lower or higher Δt are required
Water flow
The following tables indicate the minimum and maximum water flow allowed for each model. For application with
Variable Primary Flow (opt. code 143) refer to the following value for the dimensioning of the bypass line.
In case of variable flow application where the speed of the pump is managed by an external BMS (trough 0- 10V
signal) the change in water flow rate must not be exceed more than 10% of design water flow rate (at standard
conditions) per minute.
The minimum flow indicated correspond to the minimum flow allowed at minimum load for the unit. It is not
intended as minimum flow allowed for unit full load operation.
For minimum flow allowed (maximum deltaT) in full load operation refer to Selection Software.
The below values are referred to pure water (in case of glycol mixture contact factory).
Note: the performances are certified at standard conditions and with the unit operating with the nominal water
flow (corresponding to OAT 35°C; water in/out 12/7°C).
SILVER EFFICIENCY UNITS
GOLD EFFICIENCY UNITS
MODEL
Min Flow
[l/s]
Max flow
[l/s]
Min flow
[l/s]
Max flow
[l/s]
EWAT085B-SS(L)(R)A1
1.8
9.0
1.8
9.0
EWAT115B-SS(L)(R)A1
2.0
10.3
2.0
10.3
EWAT135B-SS(L)(R)A1
2.7
14.8
2.7
14.8
EWAT155B-SS(L)(R)A2
2.3
11.9
3.6
17.0
EWAT175B-SS(L)(R)A1
3.5
16.6
3.5
16.6
EWAT195B-SS(L)(R)A2
3.6
17.0
3.6
17.0
EWAT205B-SS(L)(R)A2
3.6
17.0
4.3
20.0
EWAT215B-SS(L)(R)A1
4.3
20.5
4.3
20.5
EWAT240B-SS(L)(R)A2
3.6
17.0
4.3
20.0
EWAT260B-SS(L)(R)A2
3.6
17.0
5.6
26.5
EWAT290B-SS(L)(R)A1
4.3
20.5
4.9
23.1
EWAT310B-SS(L)(R)A2
5.6
26.5
5.6
26.5
EWAT330B-SS(L)(R)A2
5.6
26.5
5.6
26.5
EWAT340B-SS(L)(R)A1
4.9
23.1
4.9
23.1
EWAT350B-SS(L)(R)A2
5.6
26.5
5.6
26.5
EWAT420B-SS(L)(R)A2
7.0
31.2
7.0
31.2
EWAT460B-SS(L)(R)A2
7.0
31.2
7.0
31.2
EWAT510B-SS(L)(R)A2
7.0
31.2
8.8
41.2
EWAT570B-SS(L)(R)A2
8.8
41.2
8.8
41.2
EWAT610B-SS(L)(R)A2
8.8
41.2
9.9
46.0
EWAT670B-SS(L)(R)A2
8.8
41.2
9.9
46.0
Minimum glycol percentage for low air ambient temperature to prevent freezing
of the hydraulic circuit
AMBIENT T [°C]
-3
-8
-15
-20
AMBIENT T [°C]
-3
-8
-15
-20
ETHYLENE GLYCOL
10%
20%
30%
40%
PROPYLENE GLYCOL
10%
20%
30%
40%
The presence of glycol in the water system will affect unit performances. Refer to the selection software for
details. All machine protection systems, such as antifreeze and low-pressure protection will need to be set in
accordance to the type and percentage of the glycol and plant requirements.
Air heat exchanger - Altitude correction factors
ELEVATION ABOVE SEA LEVEL [m]
0
300
600
900
1200
1500
1800
BAROMETRIC PRESSURE [mbar]
1013
997
942
908
875
843
812
COOLING CAPACITY CORRECTION FACTOR
1
0,993
0,986
0,979
0,973
0,967
0,96
POWER INPUT CORRECTION FACTOR
1
1,005
1,009
1,015
1,021
1,026
1,031
Maximum operating altitude is 1800 m above sea level.
Contact factory if the unit has to be installed 1000 m above the sea level.