ELECTRICAL SPECIFICATIONS
34/62
EWAT~B-SR
MODEL
EWAT085B-
SRA1
EWAT115B-
SRA1
EWAT155B-
SRA2
EWAT175B-
SRA1
EWAT195B-
SRA2
POWER SUPPLY
Phases
No.
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
207
319
316
272
482
413
Nominal running current
cooling
A
62
71
87
119
119
127
Maximum running current
A
69
96
93
137
159
193
Maximum current for wires
sizing
A
76
106
102
151
174
212
FANS
Nominal running current
cooling
A
3
5
5
6
6
8
COMPRESSORS
Phases
No.
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
Maximum running current
A
66
91
88
131
152
185
Starting method
DOL
DOL
DOL
DOL
DOL
DOL
MODEL
EWAT205B-
SRA2
EWAT215B-
SRA1
EWAT260B-
SRA2
EWAT290B-
SRA1
EWAT310B-
SRA2
POWER SUPPLY
Phases
No.
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
UNIT
Maximum inrush current
A
410
486
407
404
560
552
Nominal running current
cooling
A
143
151
151
165
189
202
Maximum running current
A
190
165
188
185
239
233
Maximum current for wires
sizing
A
209
181
207
204
263
257
FANS
Nominal running current
cooling
A
8
8
9
9
9
11
COMPRESSORS
Phases
No.
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
10%
10%
10%
10%
10%
10%
Maximum running current
A
182
157
180
177
230
222
Starting method
DOL
DOL
DOL
DOL
DOL
DOL
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: In case of inverter driven units, no inrush current at start up is experienced.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
The data are referred to the standard unit without options.
For the electrical data of the hydronic kit refer to "Options technical data"
All data are subject to change without notice. Please refer to unit nameplate data.