Daikin EWAT290B-SRA1 [41/62] Ewat b sr

Daikin EWAT290B-SSA1 [41/62] Ewat b sr
SOUND LEVELS
41/62
EWAT~B-SR
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Sound
Power
MODEL
63 Hz
125 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
db (A)
85
55.2
60.1
56.2
53.9
51.3
45.6
61.2
79
115
58.7
63.6
59.7
57.4
54.8
49.1
64.7
83
135
60.4
65.3
61.4
59.1
56.5
50.8
66.4
84
155
57.3
62.2
58.2
56.0
53.4
47.7
63.3
82
175
62.3
67.2
63.3
61.0
58.4
52.7
68.3
86
195
59.3
64.2
60.3
58.0
55.4
49.7
65.3
84
205
60.6
65.5
61.6
59.3
56.7
51.0
66.6
85
215
63.4
68.3
64.4
62.1
59.5
53.8
69.4
88
240
62.1
66.9
63.0
60.8
58.2
52.4
68.1
87
260
62.2
67.1
63.2
60.9
58.3
52.6
68.2
87
290
62.5
67.4
63.5
61.2
58.6
52.9
68.5
88
310
62.7
67.6
63.6
61.4
58.8
53.1
68.7
88
330
62.8
67.7
63.8
61.5
58.9
53.2
68.8
88
340
63.6
68.5
64.6
62.3
59.7
54.0
69.6
89
350
62.9
67.8
63.9
61.6
59.0
53.3
68.9
88
420
63.8
68.7
64.7
62.5
59.9
54.2
69.8
90
460
63.9
68.8
64.8
62.6
60.0
54.2
69.9
90
510
64.5
69.3
65.4
63.2
60.6
54.8
70.5
90
570
64.5
69.4
65.5
63.2
60.6
54.9
70.5
91
610
64.6
69.5
65.6
63.3
60.7
55.0
70.6
91
670
65.0
69.9
66.0
63.8
61.2
55.4
71.1
92
EWAT~B-XS
Sound pressure level at 1 m from the unit (rif. 2 x 10-5 Pa)
Sound
Power
MODEL
63 Hz
125 Hz
1000 Hz
2000 Hz
4000 Hz
8000 Hz
db(A)
db (A)
85
62.3
67.2
63.3
61.0
58.4
52.7
68.3
86
115
64.8
69.7
65.8
63.5
60.9
55.2
70.8
89
145
66.2
71.0
67.1
64.9
62.3
56.5
72.2
91
180
66.3
71.1
67.2
65.0
62.4
56.6
72.3
91
185
67.7
72.6
68.6
66.4
63.8
58.1
73.7
92
200
67.0
71.9
68.0
65.8
63.1
57.4
73.1
92
220
67.7
72.6
68.7
66.4
63.8
58.1
73.7
93
230
69.3
74.1
70.2
68.0
65.4
59.6
75.3
95
250
68.3
73.2
69.3
67.0
64.4
58.7
74.3
94
280
69.1
74.0
70.1
67.8
65.2
59.5
75.1
95
300
70.1
74.9
71.0
68.8
66.2
60.4
76.1
96
310
69.5
74.4
70.5
68.2
65.6
59.9
75.5
95
320
69.9
74.7
70.8
68.6
66.0
60.2
75.9
95
360
70.4
75.3
71.4
69.1
66.5
60.8
76.4
96
370
70.3
75.1
71.2
69.0
66.4
60.6
76.3
96
430
71.0
75.9
71.9
69.7
67.1
61.3
77.0
97
470
71.2
76.1
72.1
69.9
67.3
61.5
77.2
98
540
71.6
76.5
72.6
70.3
67.7
62.0
77.6
98
600
71.8
76.7
72.8
70.5
67.9
62.2
77.8
99
660
71.9
76.8
72.8
70.6
68.0
62.3
77.9
99
700
72.3
77.2
73.2
71.0
68.4
62.7
78.3
99
Sound power level (referred to evaporator 12/7°C, ambient 35°C full load operation) are measured in accordance with ISO 9614 and
Eurovent 8/1 for Eurovent certified units. The certification refers only to the overall sound power level.
The sound data in the Octave band spectrum is for intended for reference only and not considering binding.
The sound pressure is calculated from the sound power level and are for information only and not considered binding.

Содержание